Commissioning
7.2 Checks to be carried out prior to commissioning
● The machine is undamaged.
● The machine has been correctly installed and aligned, the transmission elements are
● All fixing screws, connection elements, and electrical connections have been tightened to
● The operating conditions match the data provided in accordance with the technical
● Moving parts such as the coupling move freely.
● If the second shaft extension is not in use, its feather key is secured to prevent it from being
● All touch protection measures for moving and live parts have been taken.
● The rotor can spin without coming into contact with the stator.
● The bearing insulation is not bridged.
● The grounding and equipotential bonding connections have been made correctly.
● The machine is connected so that it rotates in the direction specified.
● Appropriately configured control and speed monitoring functions ensure that the motor
● The minimum insulation resistance values are within tolerance.
● Minimum air clearances have been maintained.
● Any supplementary motor monitoring devices and equipment have been correctly
● All brakes and backstops are operating correctly.
● At the monitoring devices, the values for "Warning" and "Shutdown" are set.
● While being operated on the converter, the motor cannot exceed the specified upper speed
● The converter is correctly parameterized. The parameterization data is specified on the
74
correctly balanced and adjusted.
the specified tightening torques.
documentation, such as degree of protection, ambient temperature, etc..
thrown out, and cut back to roughly half its length if the rotor has balancing type "H"
(standard type).
cannot exceed the permissible speeds specified in the technical data. For this purpose,
compare the data on the rating plate or, if necessary, the system-specific documentation.
connected and are functioning correctly.
limit n
or undershoot the lower speed limit n
max
If the design of the motor requires connection to a particular converter type, the rating plate
will contain corresponding additional information.
rating plate of the machine. Information about the parameters is available in the operating
instructions for the converter.
.