Electrical connection
6.4 Auxiliary circuits
CAUTION
Connection of temperature sensors to intrinsically safe circuits with certified evaluation
devices
The temperature sensors may only be connected to intrinsically safe circuits with certified
evaluation devices. The maximum permissible input currents and powers according to the
EC type-examination certificate shall not be exceeded. This can otherwise result in damage.
If shielded, intrinsically safe temperature sensors are fitted in the stator winding, these must
be connected using the blue connecting terminals. The shield is grounded at the laminated
core; multiple grounding is not permitted.
6.4.4

Connecting an external fan

Preconditions
● Only use cables that comply with the relevant installation regulations regarding voltage,
● Before connecting the device, make sure that the line voltage matches the device voltage.
● Check whether the data on the fan rating plate matches the connection data.
● Cable glands are not included in the scope of delivery. Close unused cable entries,
● The line voltage must fulfill the quality criteria stipulated by DIN EN 50160 and the defined
Procedure
1. Open the terminal box of the external fan and route the cables into it. The cables are not
2. Connect the protective conductor (PE).
3. Connect the other cables to the relevant terminals, refer to the connection diagram.
66
current, insulation material, and load-carrying capacity.
otherwise, the degree of protection is not maintained.
Type
1PH818.
1 AC 200 V ... 277 V / 50Hz, 60 Hz (± 10 %)
1PH822.
1 AC 200 V ... 277 V / 50Hz, 60 Hz (± 10 %)
1PH828.
Connection values for external fans
standard voltages specified in DIN IEC 60038.
included in the scope of delivery.
Connection cables must not be subject to excessive tensile stress.
Note
For fans equipped with EC motor, the fan motor starts with a delay after the line voltage
is connected.
Supply voltage
3 AC 400 V / 50 Hz (± 10 %)
3 AC 400 V / 60 Hz (± 10 %)
3 AC 480 V / 60 Hz (± 10 %)
Current consumption
1,45 ... 1,05 A
Operating Instructions 05/2012 A5E03986435A AA
2,3 ... 1,6 A
2,55 A
2,50 A
2,50 A
SIMOTICS M-1PH8