3) Select the ExFC radio button to designate that the G4 EX is the device that
4) Next, select the Update radio button.

6.2.5 Unit operating status shut down instructions

1) Collect data from the unit.
2) Back up all of the configuration and data files.
3) While in PCCU32, click the Save and Restore Utility icon from the main
4) Within the Save and Restore Utility, click the Save Station Files button.
5) When the Save Station Files dialog box displays, verify the default name
6) When finished saving the station files, a new dialog box will offer the option
7) Remove power externally from the unit.

6.2.6 Internal PCCU connector disassembly (if installed)

1) Gain access to the termination board by loosening the countersunk hex
2) Remove the four 6-32 x .625 standoffs located at the four corners of the
3) Gently lift the termination board out of the unit. Be careful to not disconnect
4) Disconnect the cable from the termination board.

6.2.7 I/O daughter card installation

1) Gain access to the termination board by loosening the countersunk hex
2) Remove the four existing 6-32 x 625 standoffs and washers (if installed). Do
3) Install the new standoffs (6-32 x .75") and washers supplied in the kit into
Page 26
will receive the new Flash.
window toolbar. The Save and Restore Utility window will display.
and path for the files. Click the OK button. This will save the tfData drive
files.
to Restore the Station Files to the tfCold drive. Select No.
Remove power from the device, or insure the area is known to be
non-hazardous before removing any enclosure cover. For further
information, refer to the certification drawing indicated on the
device's nametag and national and local electrical codes.
socket locking set screw in the rear end cap. Use a 1/16" hex wrench, and
then unscrew the end cap.
termination board.
the PCCU ribbon cable from the termination board.
Remove power from the device, or insure the area is known to be
non-hazardous before removing any enclosure cover. For further
information, refer to the certification drawing indicated on the
device's nametag and national and local electrical codes.
socket locking set screw in the rear end cap. Use a 1/16" hex wrench, and
then unscrew the end cap.
not misplace as they will be needed later in this procedure.
the four corner mounting holes in the termination board.
2104349 rev. AD