Software Cold Boot; Figure 4-2 Lithium Battery Connector - ABB XSeries G4 6200 User Manual

Flow computer
Table of Contents

Advertisement

4.5.2 Software Cold Boot

There are two methods for initiating a software cold boot:
4.5.2.1
1) Open PCCU32. The user needs to insure that they are not connected
2) Click the 32-Bit Loader icon on the toolbar. This takes the user to the 32-Bit
3) Within the screen, the user needs to select the Reload radio button.
4) Make sure that all of the checkmarks are removed from the various software
4.5.2.2
1) Move into Entry mode within PCCU32.
2) Once this has been completed, click the Terminal icon on the PCCU32
3) Once in the Terminal window, move to the terminal prompt (->), and type in
2104349 rev. AD
Figure 4–2 Lithium battery Connector
Method 1
initially and are at the Totalflow splash screen.
Loader screen.
options. Once this has been accomplished, place a check in the options list
beside Shutdown Flash, Delete tfData and Start Flash. A prompt will display
that warns that a cold boot is occurring. Click the Yes button to initiate a
cold boot.
There is a chance that the user will see a PCCU32 dialog
box display that informs them that the Target Device Loader
is not working. The user will need to follow the dialog box
instructions to cold boot the system.
Method 2
window toolbar. This will bring up the Terminal window.
the following: BOOT=COLD. Press Enter on the keyboard to initiate the
warm boot.
J5
LITHIUM
L1
Lithium Battery
Connector
Page 4–5