Item
Monitor Alarm definition
Set frequency (RAM)
*4
Set frequency (EEPROM)
Set frequency (RAM)
*4
Set frequency
(RAM and EEPROM)
*4
*4
Setting from remote resisters can be made.
Read /
Code
Write
Number
H0000 to HFFFF: Last two alarm definitions
Read H0074 to
H0077
Refer to the alarm data table (page 72)
Read set frequency/speed from RAM or EEPROM.
⋅ H0000 to HFFFF:
H006D
Set frequency...0.01Hz increments
Speed ..............Unit r/min (when Pr.37 = 1 to 9998 or Pr.144 = 2 to
Read
⋅ When performing torque control under real sensorless vector
control or vector control with Pr.544 = "0, 1, 12, (100, 112, 114)" and
H006E
*4
Pr.804 = "3 or 5", read torque command value.
The setting range depends on Pr.804. (FR-A700 series)
Write set frequency/speed to RAM or EEPROM.
⋅ H0000 to H9C40 (0 to 400.00Hz) :
Frequency........0.01Hz increments
Write
H00ED
⋅ H0000 to H270E (0 to 9998) :
Speed ..............Unit r/min (when Pr.37 = 1 to 9998 or Pr.144 = 2 to
⋅ To change the set frequency consecutively, write data to the
inverter RAM. (Instruction code: HED)
⋅ When performing torque control under real sensorless vector
Write
H00EE
control or vector control (torque control) with Pr.544 = "0, 1, 12,
(100, 112, 114)" and Pr.804 = "3 or 5", torque command is set.
The setting range depends on Pr.804. (FR-A700 series)
DETAILS OF INPUT AND
Description
b15
b8 b7
Second alarm in past
Latest alarm
H74
Fourth alarm in past
Third alarm in past
H75
H76
Sixth alarm in past
Fifth alarm in past
Eighth alarm in past
Seventh alarm in past
H77
10, 102 to 110)
10, 102 to 110)
OUTPUT SIGNALS
b0
69