Remote Resister (Inverter (Fr-A7Nc) To Master Unit) - Mitsubishi FR-A7NC Instruction Manual

Inverter plug-in option cc-link communication function
Table of Contents

Advertisement

DETAILS OF INPUT AND
OUTPUT SIGNALS
7.2.2

Remote resister (inverter (FR-A7NC) to master unit)

(1) Remote resister definition
Device
Signal
No.
RWr0
First monitor value
Second monitor
RWr1
value
(Output frequency
Reply code
(when Pr. 544 = 0)
RWr2
Reply code 1
(when Pr. 544
0, (100))
Reply code 2
(when Pr. 544 ≠ 0, (100))
RWr3
Read data
64
When RYC is on, the monitor value specified to the lower 8 bits of the monitor code
(RWw0) is set.
When "0" is set to the upper 8 bits of the monitor code (RWw0), the current output
frequency is always set. When other than "0" is set to the upper 8 bits of the monitor
code (RWw0) and RYC is on, the monitor value specified to the upper 8 bits of the
monitor code (RWw0) is set.
)
*
*
When a value other than 9999 is set in Pr.430 under position control (Pr.800 = 3),
pulse monitor is selected. (FR-A700 series)
Turning on either RYD or RYE set the reply code corresponds to the frequency setting
command. Turning on RYF set the reply code corresponds to the instruction code of
RWw2. The value "0" is set for a normal reply and other than "0" is set for data fault,
(reply code
mode error, etc.
Lower 8bits of RWr2
Turning on either RYD or RYE set the reply code corresponds to the frequency setting
command (torque command)
Upper 8bits of RWr2
Turning on RYF set the reply code corresponds to the instruction code of RWw2.
(reply code 2
refer to page 66)
For a normal reply, the reply data to the instruction specified by the instruction code is
set.
Description
refer to page 66)
. (reply code 1
refer to page 66)