Rigging; Lifting Procedure - Trane RTHD series Installation, Operation And Maintanance

Series r helical rotery liquid chillers with heat recovery option. 175-450 ton units (60 hz), 125-410 ton units (50 hz)
Table of Contents

Advertisement

Lifting Procedure

D CAUTION
Equipment Damage!
Never use a forklift to move the unit. The skid is not de-
signed to support the unit at any one point and using
a forklift to move the equipment may cause unit dam-
age. Always position the lifting beam so that cables do
not contact the unit. Failure to do so may result in unit
damage.
Note: If absolutely necessary, the chiller can be pushed
or pulled across a smooth surface if it is bolted to
wood shipping mounts.
D WARNING
Shipping Mounts!
Do not use the threaded holes in the compressor to lift
or assist in lifting the unit. They are not intended for
that purpose and could create a dangerous situation.
Do not remove the wood mounts until the unit is in its
final location. Removal of wood shipping mounts prior
to unit final locating could result in death or serious
injury or equipment damage.
Table 12. Rigging
Unit
Designator*
E3G2G1
E3F2F3
E3D2E2
D3G2G1
D3F2F3
D3D2E2
D2G3G3 / D3G3G3
D2G2G1
D2F2F3
D2D2E2
D1G1G1
D1G2G2
D1F1F2
D1D1E1
C2F2F3
* Designator corresponds to digits 6, 7, 14, 15, 21, 22 of model number
RTHD-SVX02H-EN
A
B
3658
3353
(144.02)
(132.01)
3658
3353
(144.02)
(132.01)
3048
2743
(120.00)
(107.99)
3658
3353
(144.02)
(132.01)
3658
3353
(144.02)
(132.01)
3048
2743
(120.00)
(107.99)
3658
3353
(144.02)
(132.01)
3658
3353
(144.02)
(132.01)
3658
3353
(144.02)
(132.01)
3048
2743
(120.00)
(107.99)
3658
3353
(144.02)
(132.01)
3658
3353
(144.02)
(132.01)
3658
3353
(144.02)
(132.01)
3048
2743
(120.00)
(107.99)
3658
3353
(144.02)
(132.01)
1. When the unit is at its final location, remove the
shipping bolts that secure the unit to the wood base
mounts.
2. Rig the unit properly and lift from above or jack
the unit (alternate moving method). Use the points
shown on the rigging diagram that ships with the
unit as shown in
Figure
3. Install clevis connectors in lifting holes provided on
the unit. Attach lifting chains or cables to clevis con-
nectors as shown in
be strong enough to lift the chiller.
Dimension (mm (in))
C
D
1621
20
(63.82)
(0.79)
1612
29
(63.46)
(1.14)
1525
116
(60.04)
(4.57)
1612
99
(63.46)
(3.90)
1610
101
(63.39)
(3.98)
1523
188
(59.96)
(7.40)
1612
99
(63.46)
(3.90)
1612
99
(63.46)
(3.90)
1610
101
(63.39)
(3.98)
1523
188
(59.96)
(7.40)
1614
97
(63.54)
(3.82)
1614
97
(63.54)
(3.82)
1612
99
(63.46)
(3.90)
1524
187
60.00)
(7.36)
1610
101
63.39)
(3.98)
Installation Mechanical
10. Remove the base mounts.
Figure
10. Each cable alone must
E
661
(26.02)
(24.02)
615
(24.21)
(24.02)
612
(24.09)
(24.02)
654
(25.75)
(24.02)
617
(24.29)
(24.02)
614
(24.17)
(24.02)
654
(25.75)
(24.02)
654
(25.75)
(24.02)
617
(24.29)
(24.02)
614
(24.17)
(24.02)
661
(26.02)
(24.02)
661
(26.02)
(24.02)
622
(24.49)
(24.02)
612
(24.09)
(24.02)
617
(24.29)
(24.02)
F
610
610
610
610
610
610
610
610
610
610
610
610
610
610
610
31

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents