Trane RTHD series Installation, Operation And Maintanance page 116

Series r helical rotery liquid chillers with heat recovery option. 175-450 ton units (60 hz), 125-410 ton units (50 hz)
Table of Contents

Advertisement

Diagnostics
Table 35. Diagnostics Table
Hex
Diagnostic Name
Code
and Source
1AD
MP Application Mem-
ory CRC Error
6A1
MP: Could not Store
Starts and Hours
5FF
MP: Invalid Configu-
ration
6A2
MP: Non-Volatile
Block Test Error
69C
MP: Non-Volatile
Memory Reformat
D9
MP: Reset Has Oc-
curred
297
No Differential Re-
frigerant Pressure
1E1
Oil Flow Protection
Fault
5BE
Oil Pressure Trans-
ducer
A1
Outdoor Air Tem-
perature Sensor
D7
Over Voltage
E4
Phase Loss
E5 or
Phase Reversal
E5
E3
Phase Unbalance Se-
vere Current Imbal-
ance
116
Severity
Persistence
Immediate
Latch
Info
Latch
Immediate
Latch
Info
Latch
Info
Latch
Info
NonLatch
Immediate
Latch
Immediate
Latch
Normal
Latch
Info and Spe-
Latch
cial Action
Normal
NonLatch
Immediate
Latch
Immediate
Latch
Normal
Latch
Criteria
App software inside the MP failed its own checksum test. Possible
causes: application software in the MP is not complete - software
download to the MP was not completed successfully - or MP hard-
ware problem. Note: User should attempt to reprogram the MP if
this diagnostic occurs.
MP has determined there was an error with the previous power
down store. Starts and Hours may have been lost for the last 24
hours.
MP has an invalid configuration based on the current software
installed
MP has determined there was an error with a block in the
Non-Volatile memory. Check settings.
MP has determined there was an error in a sector of the Non-Vol-
atile memory and it was reformatted. Check settings.
The main processor has successfully come out of a reset and built
its application. A reset may have been due to a power up, install-
ing new software or configuration. This diagnostic is immediately
and automatically cleared and thus can only be seen in the His-
toric Diagnostic List in TechView
The system differential pressure was below 7.7 Psid. The occur-
rence of this diagnostic will saturate the above "Low Diff Rfgt
Press" Integral and invoke the same "Compressor Cool Down" op
mode.
The Oil Pressure Transducer for this Chiller is reading a pressure
either above its Condenser Pressure by 15 Psia or more, or below
its Evaporator Pressure 10 Psia or more for 30 seconds continu-
ously.
Bad Sensor or LLID
Bad Sensor or LLID. This diagnostic will only occur if OA sensor
is configured.OA Chilled water reset will be suspended if selected
and Tracer OA unavailable.
a. Average of all monitored Line voltages above + 10% of nom-
inal. [Must hold = + 10 % of nominal. Must trip = + 15 % of
nominal. Reset differential = min. of 2% and max. of 4%. Time
to trip = minimum of 1 min. and maximum of 5 min.) Design:
Nom. trip: 60 seconds at greater than 112.5%, + or - 2.5%,
Auto Reset at 109% or less.
a) No current was sensed on one or two of the current transform-
er inputs while running or starting (See Nonlatching Power Loss
Diagnostic for all three phases lost while running). Must hold =
20% RLA. Must trip = 5% RLA. Time to trip shall be longer than
guaranteed reset on Starter Module at a minimum, 3 seconds
maximum. Actual design trippoint is 10%. The actual design trip
time is 2.64 seconds. b) If Phase reversal protection is enabled
and current is not sensed on one or more current xformer inputs.
Logic will detect and trip in a maximum of 0.3 second from com-
pressor start.
A phase reversal was detected on the incoming current. On a
compressor startup the phase reversal logic must detect and trip
in a maximum of 0.3 second from compressor start.
A 30% Phase cCurrent Unbalance imbalance has been detected
on one phase relative to the average of all 3 phases for 90 con-
tinuous seconds.
Reset
Level
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Local
Remote
Remote
Remote
Local
Local
Local
RTHD-SVX02H-EN