Trane RTHD series Installation, Operation And Maintanance page 115

Series r helical rotery liquid chillers with heat recovery option. 175-450 ton units (60 hz), 125-410 ton units (50 hz)
Table of Contents

Advertisement

Table 35. Diagnostics Table
Hex
Diagnostic Name
Code
and Source
59D
Loss of Oil at Com-
pressor (Stopped)
C5
Low Chilled Water
Temp: Unit Off
C6
Low Chilled Water
Temp: Unit On
1AE
Low Differential Re-
frigerant Pressure
18E
Low Discharge Su-
perheat
583
Low Evaporator Liq-
uid Level
B5
Low Evaporator Re-
frigerant Pressure
FB
Low Evaporator
Refrigerant Tempera-
ture
6B3
Low Evaporator
Temp: Unit Off
198
Low Oil Flow
E2
Momentary Power
Loss
RTHD-SVX02H-EN
Severity
Persistence
Immediate
Latch
and Special
Action
Info and Spe-
NonLatch
cial Action
Immediate
NonLatch
and Special
Action
Immediate
Latch
Normal
Latch
Info
NonLatch
Immediate
Latch
Immediate
Latch
Info and Spe-
NonLatch
cial Action
Immediate
Latch
Immediate
Nonlatch
Criteria
Oil Loss Level Sensor detects a lack of oil in the oil tank feeding
the compressor for 90 seconds after EXV preposition is complet-
ed. Note: Compressor start is delayed while waiting for oil to be
detected.
The leaving chilled water temp. fell below the leaving water temp
cutout setting for 30 degree F seconds while the Chiller is in
the Stop mode, or in Auto mode with no compressors running.
Energize Evap Water pump Relay until diagnostic auto resets,
then return to normal evap pump control. Automatic reset occurs
when the temp rises 2°F (1.1°C) above the cutout setting for 30
minutes.
The chilled water temp. fell below the cutout setpoint for 30
degree F Seconds while the compressor was running. Automatic
reset occurs when the temperature rises 2 °F (1.1°C) above the
cutout setting for 2 minutes. This diagnostic shall not de-energize
the Evaporator Water Pump Output.
The system differential pressure was either below 15 Psid for
more than 164 Psid-sec, or below 23.0 Psid for 3000 Psid-sec.
The latter integral's value is not cleared for any reason including
diagnostic trip, manual reset, or power up reset (ie. Integral is
saved nonvolatily on power down). The integral will decay while
circuit is running at a max rate of -10 PSID, and while stopped at
a rate of -0.4 PSID. This same integral is associated with the op-
erating mode "Compressor Cool Down". Also see diagnostic below
While Running Normally, the Discharge Superheat was less than
12 degrees F +- 1F for more than 6500 degree F seconds.. At
startup the UCM shall ignore the Discharge Superheat for 5.
The liquid level sensor is seen to be at or near its low end of
range for 80 contiguous minutes while the compressor is running.
Design: 20% or less of bit count corresponding to -21.2 mm or
less liquid level for 80 minutes)
The Evaporator Refrigerant Pressure dropped below 10 psia just
prior to compressor start. The pressure fell below 10 psia while
running but before the 1 minute ignore time had expired or fell
below 16 Psia after the 1 minute ignore time had expired.
a. The inferred Saturated Evap Refrigerant Temperature (calculat-
ed from suction pressure transducer( s)) dropped below the Low
Refrigerant Temperature Cutout Setpoint for 450°F-sec (10°F-sec
max rate) while the circuit was running after the ignore period
had expired. The integral is held at zero for the 1 minute ignore
time following the circuit startup and the integral will be limited
to never trip in less than 45 seconds, i.e. the error term shall be
clamped to 10°F. The minimum LRTC setpoint is -5°F (18.7 Psia)
the point at which oil separates from the refrigerant. b. During
the timeout of the trip integral, the unload solenoid(s) of the run-
ning compressors on the circuit, shall be energized continuously
and the load solenoid shall be off. Normal load/unload operation
will be resumed if the trip integral is reset by return to temps
above the cutout setpoint.
The evap sat temp fell below the water temp cutout setting while
the respective evap liquid level was greater than -21.2mm for
30 degree F seconds while Chiller is in the Stop mode, or in Auto
mode with no compressors running. Energize Evap Water pump
Relay until diagnostic auto resets, then return to normal evap
pump control. Automatic reset occurs when either the evap temp
rises 2°F (1.1°C) above the cutout setting or the liquid level falls
below - 21.2mm for 30 minutes
The oil pressure was out of the acceptable pressure range for 15
seconds, while the Delta Pressure was greater than 23.8 Psid.:
Acceptable range is 0.50 > (PC-Po) / (PC-PE) for the first 2.5
minutes of operation, and 0.40 > (PC-Po) / (PC-PE) thereafter,
Momentary Power Loss option disabled: No effect. Momentary
Power Loss option enabled: A loss of power on three line cycles
or more was detected. Diagnostic is reset in 30 seconds. See
Momentary Power Loss Protection specification for additional
information.
Diagnostics
Reset
Level
Local
Remote
Remote
Remote
Remote
Remote
Local
Remote
Remote
Local
Remote
115