Trane RTHD series Installation, Operation And Maintanance page 112

Series r helical rotery liquid chillers with heat recovery option. 175-450 ton units (60 hz), 125-410 ton units (50 hz)
Table of Contents

Advertisement

Diagnostics
Table 35. Diagnostics Table
Hex
Diagnostic Name
Code
and Source
6B6
Comm Loss:
Condenser Leaving
Water Temperature
5F2
Comm Loss:
Condenser Rfgt
Pressure
6B6
Comm Loss:
Condenser Rfgt
Pressure Output
5F9
Comm Loss:
Condenser Water
Pump Starter
694
Comm Loss:
Electronic Expansion
Valve 1
695
Comm Loss:
Electronic Expansion
Valve 2
5DE
Comm Loss:
Emergency Stop
5E4
Comm Loss: Evap
Entering Water Temp
5E3
Comm Loss: Evap
Leaving Water Temp
688
Comm Loss:Evapora-
tor Rfgt Liquid Level
5F0
Comm Loss:Evapo-
rator Rfgt Pressure
5E1
Comm Loss: Ext
Ice Building Control
Input
5DD
Comm Loss:External
Auto/Stop
6B6
Comm Loss: External
Base Load Enable
6B6
Comm Loss: External
Base Load Setpoint
Input
5E9
Comm Loss: Exter-
nal Chilled Water
Setpoint
5EA
Comm Loss:
External Current
Limit Setpoint
5EB
Comm Loss: High
Pressure Cutout
Switch
5FA
Comm Loss: Ice-
Making Status
69D
Comm Loss: Local
BAS Interface
6B6
Comm Loss: Master
Oil Line Solenoid
Valve
6B6
Comm Loss: Oil Loss
Level Input
5F4
Comm Loss: Oil
Pressure
112
Severity
Persistence
Info
Latch
Normal
Latch
Info
Latch
Info
Latch
Normal
Latch
Normal
Latch
Normal
Latch
Info and Spe-
Latch
cial Action
Normal
Latch
Normal
Latch
Normal
Latch
Normal
Latch
Normal
Latch
Info and Spe-
Latch
cial Action
Info and Spe-
Latch
cial Action
Info and Spe-
NonLatch
cial Action
Info and Spe-
NonLatch
cial Action
Normal
Latch
Normal
Latch
Info and Spe-
NonLatch
cial Action
Normal
Latch
Normal
Latch
Normal
Latch
Criteria
Continual loss of communication between the MP and the Func-
tional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the Func-
tional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the Func-
tional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the Func-
tional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the Func-
tional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the Func-
tional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the Func-
tional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the Func-
tional ID has occurred for a 30 second period. Chiller shall
remove any Return or Constant Return Chilled Water Reset, if it
was in effect. Apply slew rates per Chilled Water Reset spec.
Continual loss of communication between the MP and the Func-
tional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the Func-
tional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the Func-
tional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the Func-
tional ID has occurred for a 30 second period. Chiller shall revert
to normal (non-ice building) mode regardless of last state.
Continual loss of communication between the MP and the Func-
tional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the Func-
tional ID has occurred for a 30 second period. The external base
load input is removed from the arbitration to enable Base Load-
ing.
Continual loss of communication between the MP and the Func-
tional ID has occurred for a 30 second period. The external base
load setpoint input is removed from the arbitration to establish
the Base LoadingSetpoint.
Continual loss of communication between the MP and the Func-
tional ID has occurred for a 30 second period. Chiller shall discon-
tinue use of the External Chilled Water Setpoint source and revert
to the next higher priority for setpoint arbitration
Continual loss of communication between the MP and the Func-
tional ID has occurred for a 30 second period. Chiller shall discon-
tinue use of the External Current limit setpoint and revert to the
next higher priority for Current Limit setpoint arbitration
Continual loss of communication between the MP and the Func-
tional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the Func-
tional ID has occurred for a 30 second period. Chiller shall revert
to normal (non-ice building) mode regardless of last state.
Continual loss of communication between the MP and the Func-
tional ID has occurred for a 30 second period. Use the last values
sent from BAS
Continual loss of communication between the MP and the Func-
tional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the Func-
tional ID has occurred for a 30 second period.
Continual loss of communication between the MP and the Func-
tional ID has occurred for a 30 second period.
Reset
Level
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
Remote
RTHD-SVX02H-EN