PRECAUTIONS FOR USE OF THE INVERTER
This chapter explains the precautions for use of this product.
Always read the instructions before use.
3.1
Electro-magnetic interference (EMI) and leakage
currents
3.1.1

Leakage currents and countermeasures

Capacitances exist between the inverter I/O cables, other cables and earth and in the motor, through which a leakage current
flows. Since its value depends on the static capacitances, carrier frequency, etc., low acoustic noise operation at the increased
carrier frequency of the inverter will increase the leakage current. Therefore, take the following countermeasures. Select the
earth leakage current breaker according to its rated sensitivity current, independently of the carrier frequency setting.
 To-earth (ground) leakage currents
Leakage currents may flow not only into the inverter's own line but also into the other lines through the earthing (grounding)
cable, etc. These leakage currents may operate earth leakage circuit breakers and earth leakage relays unnecessarily.
 Countermeasures
• If the carrier frequency setting is high, decrease the Pr.72 PWM frequency selection setting.
Note that motor noise increases. Selecting Pr.240 Soft-PWM operation selection makes the sound inoffensive.
• By using earth leakage circuit breakers designed for harmonic and surge suppression in the inverter's own line and other
line, operation can be performed with the carrier frequency kept high (with low noise).
NOTE
• Long wiring will increase the leakage current.
• High motor capacity will increase the leakage current. The leakage current of the 400 V class is larger than that of the 200 V
class.
 Line-to-line leakage currents
Harmonics of leakage currents flowing in static capacitances between the inverter output cables may operate the external
thermal relay unnecessarily. When the wiring length is long (50 m or more) for the 400 V class small-capacity models, the
external thermal relay is likely to operate unnecessarily because the ratio of the leakage current to the rated motor current
increases.
 Line-to-line leakage current example (400 V class)
Motor capacity
(kW)
0.4
1.1
0.75
1.9
1.5
3.5
2.2
4.1
3.7
6.4
5.5
9.7
7.5
12.8
48
3. PRECAUTIONS FOR USE OF THE INVERTER

3.1 Electro-magnetic interference (EMI) and leakage currents

Rated motor
current(A)
Wiring length 50 m
620
680
740
800
880
980
1070
Leakage current (mA)
Wiring length 100 m
1000
1060
1120
1180
1260
1360
1450
Condition
• Motor: SF-JR 4P
• Carrier frequency: 14.5 kHz
2
• Cable: 2 mm
, 4 cores
• Cabtyre cable