Inverter Output Shutoff - Mitsubishi Electric FR-CS84-012 Instruction Manual

Freqrol-cs80
Hide thumbs Also See for FR-CS84-012:
Table of Contents

Advertisement

• Refer to the following table and set the parameters.
Signal
Setting
name
Pr.59 = 0 (initial value)
0
RL
Pr.59 ≠ 0
Pr.59 = 0 (initial value)
1
RM
Pr.59 ≠ 0
Pr.59 = 0 (initial value)
2
RH
Pr.59 ≠ 0
3
RT
Second function selection
4
AU
Terminal 4 input selection
5
JOG
JOG operation selection
7
OH
External thermal relay input
15-speed selection (combination with three speeds RL, RM, and
8
REX
RH)
10
X10
Inverter run enable (FR-HC2/FR-CV connection)
14
X14
PID control valid
24
MRS
Output stop
STP
25
Start self-holding selection
(STOP)
37
X37
Traverse function selection
Forward rotation command (assigned to STF terminal (Pr.178)
60
STF
only)
Reverse rotation command (assigned to STR terminal (Pr.179)
61
STR
only)
62
RES
Inverter reset
9999
No function
*1
When Pr.59 Remote function selection ≠ "0", functions of the RL, RM, and RH signals are changed as shown in the table.
*2
The OH signal is activated when the relay contact is open.
NOTE
• The same function can be assigned to two or more terminals. In this case, the logic of terminal input is OR.
• The priorities of the speed commands are defined as follows: JOG > multi-speed setting (RH, RM, RL, REX) > PID (X14).
• When the Inverter run enable (X10) signal is not assigned, the RT signal performs the same function.
• The same terminals are used to assign the multi-speed (7-speed) setting and the remote setting. The multi-speed setting and
the remote setting cannot be assigned separately.
• When the terminal assignment is changed with Pr.178 to Pr.182 (Input terminal function selection), wiring may be mistaken
due to different terminal name and signal contents, or may affect other functions. Set parameters after confirming the function
of each terminal.
5.8.6

Inverter output shutoff

The inverter output can be shut off with the MRS signal. The logic of the MRS signal can also be selected.
Pr.
Name
17
MRS input selection
T720
Function
Low-speed operation command
*1
Remote setting (setting clear)
Middle-speed operation
command
*1
Remote setting (deceleration)
High-speed operation command
*1
Remote setting (acceleration)
*2
Initial
Setting range
value
0
2
0
4
Related parameter
Pr.4 to Pr.6, Pr.24 to Pr.27,
Pr.232 to Pr.239
Pr.59
Pr.4 to Pr.6, Pr.24 to Pr.27,
Pr.232 to Pr.239
Pr.59
Pr.4 to Pr.6, Pr.24 to Pr.27,
Pr.232 to Pr.239
Pr.59
Pr.44, Pr.45, etc.
Pr.267
Pr.15, Pr.16
Pr.9
Pr.4 to Pr.6, Pr.24 to Pr.27,
Pr.232 to Pr.239
Pr.30
Pr.127 to Pr.134, Pr.575 to
Pr.577
Pr.17
Pr.250
Pr.592 to Pr.597
Pr.250
Pr.250
Pr.75
Description
Normally open input
Normally closed input (NC contact input specification)
External terminal: Normally closed input (NC contact input
specification)
Communication: Normally open input
5.8 (T) Multi-function input terminal parameters
2
Refer to
page
109
2
96
109
3
96
109
96
4
93
131
108
5
112
109
118
6
152
143
7
145
151
145
8
145
85
9
10
143
5. PARAMETERS