• When the set point is set at Pr.133, the setting frequency of C2 (Pr.902) is equivalent to 0% and the setting frequency of Pr.125
(Pr.903) is equivalent to 100%.
• Measured value input calibration
1.
Apply the input (for example, 4 mA) of measured value 0% across terminals 4 and 5.
2.
Perform calibration by
3.
Apply the input (for example, 20 mA) of measured value 100% across terminals 4 and 5.
4.
Perform calibration by
NOTE
• Set the frequencies set at C5 (Pr.904) and Pr.126 to each of the same values set at C2 (Pr.902) and Pr.125.
• The following figure shows the results of having performed the calibration above.
[Set point setting]
(%)
100
0
0
Parameters referred to
Pr.59 Remote function selection
Pr.73 Analog input selection
Pr.79 Operation mode selection
Pr.178 to Pr.182 (Input terminal function selection)
Pr.195 (Output terminal function selection)
C2 (Pr.902) to C7 (Pr.905) Frequency setting voltage (current) bias/gain
158
5. PARAMETERS
5.10 (A) Application parameters
, enter the frequency (for example, 60 Hz) to be output by the inverter when the deviation is 100%.
, set the voltage value at 100%.
.
C6 (Pr.904)
.
C7 (Pr.905)
(%)
100
0
0
5
(V)
page 96
page 131
page 100
page 142
page 126
[Measured value]
4
20
(mA)
page 134
[Manipulated variable]
Manipulated variable (Hz)
60
0
0
100 Deviation (%)