 Multi-speed setting for 4th speed or more (Pr.24 to Pr.27, Pr.232 to Pr.239)
• The frequency from 4th speed to 15th speed can be set according to the combination of the RH, RM, RL, and REX signals.
Set the running frequencies in
• For the terminal used for REX signal input, set "8" in any of
function.
Forward
Inverter
rotation
STF
REX
RH
RM
RL
SD
*1
When the RH, RM and RL signals are OFF and the REX signal is ON while Pr.232 Multi-speed setting (speed 8) = "9999", the inverter runs at
the frequency set in Pr.6.
NOTE
• The priority of the frequency commands given by the external signals are "JOG operation > multi-speed operation > terminal
4 analog input > pulse train input > terminal 2 analog input". (For details on frequency commands given by analog input, refer
to
page
134.)
• The multi-speed setting for 4th speed or more is enabled in the External operation mode or PU/External combined operation
mode (when Pr.79 = "3 or 4").
• Multi-speed parameters can also be set during PU operation or External operation.
• The settings of Pr.24 to Pr.27, Pr.232 to Pr.239 are not prioritized.
• When Pr.59 Remote function selection ≠ "0", the multi-speed setting is disabled since the RH, RM, and RL signals are used
for remote setting.
• Use Pr.73 Analog input selection to select the characteristic of terminal 2 (terminal to input compensation voltage (0 to ±5 V
/ 0 to ±10 V)).
• Changing the terminal assignment using Pr.178 to Pr.182 (Input terminal function selection) may affect the other functions.
Set parameters after confirming the function of each terminal.
Parameters referred to
Pr.15 Jog frequency
page 108
page 96
Pr.59 Remote function selection
page 131
Pr.73 Analog input selection
page 100
Pr.79 Operation mode selection
Pr.178 to Pr.182 (Input terminal function selection)
Pr.24 to Pr.27, Pr.232 to Pr.239
10
2
Frequency setting
potentiometer
5
page 142
. (In the initial status, 4th to 15th speeds are invalid.)
Pr.178 to Pr.182 (Input terminal function selection)
Speed 10
Speed 5
Speed 6
Speed 9
Speed 4
Speed 8
Speed 7
ON
ON
ON
RH
ON
ON
ON
ON ON
RM
ON
ON
ON
RL
ON
ON
ON ON ON ON ON ON
REX
*1
5.5 (D) Operation command and frequency command
to assign the
Speed 11
Speed 12
Speed 13
Speed 14
Speed 15
Time
ON ON ON ON
ON ON
ON
ON
ON
5. PARAMETERS
2
2
3
4
5
6
7
8
9
10
111