Johnson Controls TEC2003-3 Installation Manual page 8

Tec series multi-stage wireless thermostat controller
Table of Contents

Advertisement

Table 4: Installer Configuration Menu (Part 3 of 4)
Parameter
Description and Default
Appearing
on Display
Frost pr
Provides a minimum heating
setpoint of 5.5°C/42.0°F to prevent
freezing in the zone controlled by
the thermostat controller.
Default: off
2
Sets the Occupied and Unoccupied
Heat max
maximum Heating setpoint values.
Default: 32.0°C/90.0°F
2
Sets the Occupied and Unoccupied
Cool min
minimum Cooling setpoint values.
Default: 12.0°C/54.0°F
Anticycl
Anti-Short Cycle timer sets the
minimum on/off times for heating
and cooling stages.
Default: 2.0 min
Heat cph
Sets the maximum number of
Heating cycles per hour.
Default: 4.0
Cool cph
Sets the maximum number of
Cooling cycles per hour.
Default: 4.0
Deadband
Sets the minimum deadband
between the heating and cooling
setpoints.
Default: 1.0C°/2.0F°
Fan cont
Determines how the fan is activated
in response to a call for heating or
cooling.
Default: on
Fan del
Fan delay extends fan operation
after a heating or cooling cycle has
ended.
Default off
TOccTime
Sets the duration of the Temporary
Occupancy Time when the heating
or cooling setpoints in the Occupied
mode are established by:
an Override Function enabled in
the Main User Menu (when the
thermostat controller is in the
Unoccupied mode)
a temporary heating or cooling
setpoint
default: 3.0 hrs
8
TEC2003-3 Multi-Stage Wireless Thermostat Controller Installation Instructions
Selection Options
(on): Enabled
(off): Disabled
Range: 4.5°C/40.0°F/to 32.0°C/90.0°F
Range: 12.0°C/54.0°F to 37.5°C/100.0°F
Range: 0.0 to 5.0 min adjustable in 1-minute increments
Set the anti-short cycle timer to 0.0 min for equipment that already
has its own anti-short cycle timer.
Range: 3.0 to 8.0 cycles per hour
Range: 3.0 or 4.0 cycles per hour
Range: 1.0C°/2.0F° to 2.0C°/4.0F° adjustable in 0.5C°/1.0F°
increments
(off): Enables the thermostat controller to activate the fan in
response to a call for cooling only.
(on): Enables the thermostat controller to activate the fan in
response to a call for heating or cooling.
When there is a call for auxiliary heating, the fan is activated by the
equipment fan and limit control.
(on): Extends fan operation by 60 seconds after a heating or cooling
cycle has ended.
(off): No extension of fan operation after a heating or cooling cycle
has ended.
The fan delay is only active when the fan is in the Auto mode.
Range: 0.0 to 12.0 hrs adjustable in 1-hour increments