Endress+Hauser Cerabar S PMC71 Manual

Endress+Hauser Cerabar S PMC71 Manual

Process pressure measurement pressure transmitter with ceramic and metal sensors overload-resistant and function-monitored; communication via hart, profibus pa or foundation fieldbus
Hide thumbs Also See for Cerabar S PMC71:
Table of Contents

Advertisement

Technical Information
Cerabar S PMC71, PMP71, PMP75
Process pressure measurement
Pressure transmitter with ceramic and metal sensors
Overload-resistant and function-monitored; Communication via
HART, PROFIBUS PA or FOUNDATION Fieldbus
Application
The Cerabar S pressure transmitter is used for the
following measuring tasks:
• Absolute pressure and gauge pressure in gases, steams
or liquids in all areas of process engineering and
process measurement technology
• Level, volume or mass measurements in liquids
• High process temperature
– without diaphragm seals up to 150 °C (302 °F)
– with typical diaphragm seals up to 400 °C (752 °F)
• High pressure up to 700 bar (10500 psi)
• MID part certificate as per OIML R117-1 Edition 2007
(E) and EN 12405-1/A1 Edition 2006
• International usage thanks to a wide range of approvals
TI00383P/00/EN/15.12
No 71185798
Your benefits
• Very good reproducibility and long-term stability
• High reference accuracy: up to ±0.075 %,
as PLATINUM version: ±0.05 %
• Turn down up to 100:1, higher on request
• Used for process pressure monitoring up to SIL3,
certified to IEC 61508 by TÜV SÜD
®
• HistoROM
/M-DAT memory module
• Function-monitored from the measuring cell to the
electronics
• Continuous modularity for differential pressure,
hydrostatics and pressure (Deltabar S – Deltapilot S –
Cerabar S), e.g.
– replaceable display
– universal electronics
• Quick commissioning with Quick Setup menu
• Menu-guided operation
• Extensive diagnostic functions
• Device versions compliant with ASME-BPE
• Usage in drinking water: NSF

Advertisement

Table of Contents
loading

Summary of Contents for Endress+Hauser Cerabar S PMC71

  • Page 1 Technical Information Cerabar S PMC71, PMP71, PMP75 Process pressure measurement Pressure transmitter with ceramic and metal sensors Overload-resistant and function-monitored; Communication via HART, PROFIBUS PA or FOUNDATION Fieldbus Application Your benefits The Cerabar S pressure transmitter is used for the •...
  • Page 2: Table Of Contents

    Installation instructions ....... 75 Thermal change of the zero output and the output span – Endress+Hauser...
  • Page 3 Pressure ......... . . 95 Endress+Hauser...
  • Page 4: Function And System Design

    OPL: over pressure limit; dependent on the lowest-rated element, with regard to pressure, of the selected components High-temperature version "T" for feature 100 "Additional option 1" or for feature 110 "Additional option 2" PMP71 and PMP75: lower temperatures on request Endress+Hauser...
  • Page 5: Measuring Principle

    • Depending on the version, can be used for process pressures up to 400 bar (6000 psi) and extreme process temperatures • High long-term stability • Guaranteed overload resistance up to 4 times the nominal pressure • Secondary containment for enhanced integrity Endress+Hauser...
  • Page 6: Level Measurement (Level, Volume And Mass)

    • 4 to 20 mA with HART communication protocol • PROFIBUS PA – The Endress+Hauser devices meet the requirements of the FISCO model. – Due to the low current consumption of 13 mA ± 1 mA, the following number of devices can be operated on one bus segment if installing as per FISCO: –...
  • Page 7: Input

    OPL: over pressure limit depends on the lowest-rated element, with regard to pressure, of the selected components. Version in the order code → see also → ä 79 ff, feature 40 "Sensor range; Sensor over pressure limit (= OPL)" Turn down > 100:1 on request or can be set at the device Endress+Hauser...
  • Page 8 PMP75. → ä 75, "Filling oil" section. Version in the order code → ä 79 ff, feature 40 "Sensor range; Sensor over pressure limit (= OPL)" Turn down > 100:1 on request or can be set at the device PMP71 only, PMP75 on request Endress+Hauser...
  • Page 9 The vacuum resistance applies for the measuring cell under reference operating conditions. Version in the order code → ä 79 ff, feature 40 "Sensor range; sensor over pressure limit (= OPL)" Max. WP for gas and liquid applications suitable for custody transfer measurement Endress+Hauser...
  • Page 10: Explanation Of Terms

    This span is based on the zero point. P01-PMx7xxxx-05-xx-xx-xx-008 Example: 1 bar (15 psi) measuring cell Set span Zero-based span Nominal value i upper range limit (URL) Nominal measuring range Sensor measuring range Lower range limit Upper range limit Lower range value Upper range value Endress+Hauser...
  • Page 11: Output

    Power supply 10.5 (11.5) to 45 V DC for devices for non-hazardous areas, 1/2 D, 1/3 D, 2 G Ex d, 3 G Ex nA, FM XP, FM DIP, FM NI, CSA XP, CSA dust ignition proof, NEPSI Ex d Power supply 11 (12) to 45 V DC for PMC71, Ex d[ia], NEPSI Ex d[ia] Maximum load resistance Lmax Supply voltage Endress+Hauser...
  • Page 12: Resolution

    • HART commands: 3 to 4 per second on average. The Cerabar S commands the BURST MODE function for cyclic value transmission via the HART communication protocol. Response time ≤ 250 ms Cycle time (update time) On average 250 to 330 ms. Endress+Hauser...
  • Page 13: Dynamic Behavior, Profibus Pa

    • Via onsite display, handheld terminal or PC with operating program, continuous from 0 to 999 s • Additionally for HART and PROFIBUS PA: via DIP switch on the electronic insert, switch position "on" = set value and "off" • Factory setting: 2 s Endress+Hauser...
  • Page 14: Data Of The Foundation Fieldbus Interface

    • Pressure peakhold indicator (channel 4) • Counter for max. pressure transgressions (channel 5) Diagnostic Block Contains diagnostic information Error code via DI channels (channel 0 to 16) Display Block Contains parameters to configure the onsite display No output values Endress+Hauser...
  • Page 15 Analog Alarm This block contains all process alarm conditions 35 ms standard Block (working like a comparator) and represents them at the output. Additional function block information: Instantiate Function Block Number of instantiate blocks Endress+Hauser...
  • Page 16: Power Supply

    • Use a twisted, shielded two-wire cable, preferably cable type A Note! For further information on the cable specifications, see Operating Instructions BA00034S "PROFIBUS DP/PA: Guidelines for planning and commissioning", the PNO Guideline 2.092 PROFIBUS PA User and Installation Guideline" and IEC 61158-2 (MBP). Endress+Hauser...
  • Page 17 Not assigned Signal – Earth A0011175 Endress+Hauser offers the following accessories for devices with an M12 plug: Plug-in jack M 12x1, straight • Material: body PA; slotted nut CuZn, nickel-plated • Degree of protection (fully locked): IP67 • Order number: 52006263 Plug-in jack M 12x1, elbowed •...
  • Page 18 – Delivery status – Minimum supply voltage: 11.5 V DC – Measuring 4 to 20 mA test signal via the plus and test terminal: Test Test not possible. – Minimum supply voltage: 10.5 V DC Endress+Hauser...
  • Page 19: Supply Voltage

    → ä 79 ff, feature 30 "Housing; Cable entry; Protection". Cable entry Cable specification • Endress+Hauser recommends using shielded, twisted-pair two-wire cables. • Terminals for core cross-sections 0.5 to 2.5 mm (20 to 14 AWG) • Cable outer diameter: 5 to 9 mm (0.2 to 0.35 in) depends on the used cable gland (→ ä 18) Without influence on 4 to 20 mA signal up to ±...
  • Page 20: Performance Characteristics - General

    Device rotated 180°, process connection pointing upwards. The value is doubled for devices with inert oil. Note! Position-dependent zero shift can be corrected. → ä 25, "General installation instructions" section and → ä 75 ff, "Installation instructions, diaphragm seal systems" section Endress+Hauser...
  • Page 21: Performance Characteristics - Ceramic Process Isolating Diaphragm

    1 bar (15 psi), 2 bar (30 psi), 4 bar (60 psi), ±0.2 ±0.51 10 bar (150 psi), 40 bar (600 psi) Warm-up period – PMC71 • 4 to 20 mA HART: < 10 s • PROFIBUS PA: 6 s • FOUNDATION Fieldbus: 50 s Endress+Hauser...
  • Page 22: Pmc71

    250 mbar (3,75 psi), 400 mbar (6 psi) 1 bar (15 psi), 2 bar (30 psi), 4 bar (60 psi), ±(0.088 x TD + 0.040) ±(0.75 x TD) 10 bar (150 psi) ±(0.088 x TD + 0.040) ±(0.50 x TD) 40 bar (600 psi) Endress+Hauser...
  • Page 23: Performance Characteristics - Metallic Process Isolating Diaphragm

    2 bar (30 psi) ±0.45 ±0.15 4 bar (60 psi) ±0.3 10 bar (150 psi), ±0.15 ±0.15 40 bar (600 psi) ±0.25 ±0.25 100 bar (1500 psi) ±0.3 ±0.3 400 bar (6000 psi) ±0.3 ±0.3 700 bar (10500 psi) Endress+Hauser...
  • Page 24: Total Error - Pmp71

    100 bar (1500 psi) ±(0.35 x TD + 0.02) x 5 ±(0.7 x TD + 0.04) x 5 400 bar (6000 psi) ±(0.4 x TD + 0.03) x 5 ±(0.7 x TD + 0.04) x 5 700 bar (10500 psi) Endress+Hauser...
  • Page 25: Operating Conditions (Installation)

    • The housing of the Cerabar S can be rotated 380°. See → ä 27, "Turning the housing" section. • Endress+Hauser offers a mounting bracket for installing the device on pipes or walls. → See also → ä 26, "Wall and pipe-mounting" section.
  • Page 26: Measuring Arrangement For Devices With Diaphragm Seals - Pmp75

    – PMP75 Wall and pipe-mounting Endress+Hauser offers a mounting bracket for installing the device on pipes or walls. See also → ä 79 ff, feature 110, "Additional option 2" or separate accessory (part number: 71102216). For the dimensions, see → ä 63.
  • Page 27: Turning The Housing

    • Good, accessible device operation • Optimum readability of the onsite display (optional). max. 380° P01-PMx7xxxx-17-xx-xx-xx-000 Aligning the housing by releasing the setscrew T14 housing: 2 mm (0.08 in) Allen screw; T17 housing: 3 mm (0.12 in) Allen screw Endress+Hauser...
  • Page 28: Oxygen Applications

    "Ordering information PMC71", feature 80 "Seal", version "L" and "M". Ultrapure gas applications Endress+Hauser also offers devices for special applications, such as ultrapure gas, cleaned from oil and grease. No special restrictions regarding the process conditions apply to these devices.
  • Page 29: Operating Conditions (Environment)

    For high-temperature applications, either a PMP75 with a temperature isolator or with a capillary can be used. If vibrations also occur in the application, Endress+Hauser recommends using a PMP75 with a capillary. If a PMP75 with a temperature isolator or capillary is used, we recommend a suitable retaining unit for mounting (see "Wall and pipe-mounting"...
  • Page 30: Electromagnetic Compatibility

    • Surge current check î = 20 kA as per DIN EN 60079-14: 8/20 μs satisfied • Arrester AC current check I = 10 A satisfied → ä 79 ff, feature 100 "Additional option 1" and feature 110 "Additional option 2", version "M Overvoltage protection". Note! Devices with integrated overvoltage protection must be grounded. Endress+Hauser...
  • Page 31: Operating Conditions (Process)

    Extreme jumps in temperature can result in temporary measuring errors. Temperature compensation takes effect after several minutes. Internal temperature compensation is faster the smaller the jump in temperature and the longer the time interval involved. For further information please contact your local Endress+Hauser Sales Center. PMP71 (with metallic process isolating diaphragm) Description...
  • Page 32: Pressure Specifications

    With regard to their stability-temperature property, the materials 1.4435 and 1.4404 are grouped together under 13EO in EN 1092-1: 2001 Tab. 18. The chemical composition of the two materials can be identical. The equation does not apply for PMP71 and PMP75 with a 40 bar (600 psi) or 100 bar (1500 psi) measuring cell. Endress+Hauser...
  • Page 33: Mechanical Construction

    P01-PMx7xxxx-06-00-xx-xx-001 Front view, left-hand side view, top view → Installation height H, see process connection in question. Housing weight → ä 63. Note! For custody transfer applications, the cover clamp screws have to be locked with seal wire. Endress+Hauser...
  • Page 34: Process Connections Pmc71 (With Ceramic Process Isolating Diaphragm)

    Material version RG: PVDF (max.: 15 bar (225 psi), –10 to +60 °C/+14 to +140 °F) - only mount with a mounting bracket (→ ä 26); Weight: 0.63 kg (1.39 lbs) Thread ANSI 1/2 FNPT; Material version RH: AISI 316L, version RJ: Alloy C276, version RK: Monel; Weight: 0.63 kg (1.39 lbs) Endress+Hauser...
  • Page 35 (Ex d = 311 mm (12.2 in)) PMC71 high-temperature version 235 mm (9.25 in) 251 mm (9.88 in) PMC 71 high-temperature version with 305 mm (12 in) 321 mm (12.6 in) Ex d[ia], CSA XP or FM XP (Ex d = 391 mm (15.4 in)) Endress+Hauser...
  • Page 36 Installation height H for devices with threaded connection and flush-mounted process isolating diaphragm Description T14 housing T17 housing PMC71/PMC71 high-temperature version 215 mm (8.46 in) 231 mm (9.09 in) PMC71/PMC71 high-temperature version: 280 mm (11 in) 296 mm (11.7 in) with Ex d[ia], CSA XP or FM XP Endress+Hauser...
  • Page 37 The roughness of the surface in contact with the media, including the raised face of the flanges (all standards) made of Hastelloy C, Monel or tantalum, is Ra 0.8 μm (31.5 μin). Lower surface roughness on request. Designation as per DIN 2527 in brackets Housing weight → ä 63 Max.: 15 bar (225 psi), –10 to +60 °C (+14 to +140 °F) Endress+Hauser...
  • Page 38 Combination of AISI 316 for required pressure resistance and AISI 316L for required chemical resistance (dual rated) ECTFE coating on AISI 316/316L. When operating in hazardous areas, avoid electrostatic charge of the plastic surfaces. Max.: 15 bar (225 psi), –10 to +60 °C (+14 to +140 °F) Endress+Hauser...
  • Page 39 Housing weight see → ä 63 Installation height H for devices with flange Description T14 housing T17 housing PMC71 215 mm (8.46 in) 231 mm (9.09 in) PMC71 with Ex d[ia], CSA XP or FM XP 280 mm (11 in) 296 mm (11.7 in) Endress+Hauser...
  • Page 40 Installation height H for devices with hygienic connection and flush-mounted process isolating diaphragm Description T14 housing T17 housing PMC71/PMC71 high-temperature version 215 mm (8.46 in) 231 mm (9.09 in) PMC71/PMC71 high-temperature version: 280 mm (11 in) 296 mm (11.7 in) with Ex d[ia], CSA XP or FM XP Endress+Hauser...
  • Page 41: Process Connections Pmp71

    700 bar (10500 pis) = 3.2 mm (0.13 in) Material version RD: AISI 316L, version RE: Alloy C276; weight: 0.6 kg (1.32 lbs) Thread ANSI 1/2 FNPT; Material version RH: AISI 316L, version RJ: Alloy C276; weight: 0.7 kg (1.54 lbs) Endress+Hauser...
  • Page 42 Installation height H for devices with threaded connection and internal process isolating diaphragm T14 housing T17 housing Height H 165 mm (6.5 in) 181 mm (7.13 in) Note! The versions with a 700 bar (10500 psi) sensor are approx. 20 mm (0.79 in) higher. Endress+Hauser...
  • Page 43 Material version 2A: AISI 316L, version 2B: Alloy C276; weight: 0.7 kg (1.54 lbs) Thread ANSI 1 1/2 MNPT; Material version 2D: AISI 316L, version 2E: Alloy C276; weight: 1.0 kg (2.21 lbs) Thread ANSI 2 MNPT Material version 2G: AISI 316L, version 2H: Alloy C276; weight: 1.3 kg (2.87 lbs) Endress+Hauser...
  • Page 44 1 1/2 MNPT 165 mm (6.5 in) 181 mm (7.13 in) 2 MNPT 159 mm (6.26 in) 175 mm (6.89 in) M 20x1.5 163 mm (6.42 in) 179 mm (7.05 in) M 44x1.25 170 mm (6.69 in) 186 mm (7.32 in) Endress+Hauser...
  • Page 45 Housing weight → ä 63 With these process connections the raised face is smaller than described in the standard. Due to a smaller raised face a special seal must be used. Refer to a manufacturer of seals or your local Endress+Hauser Sales Center. Endress+Hauser...
  • Page 46 With these process connections the raised face is smaller than described in the standard. Due to a smaller raised face a special seal must be used. Refer to a manufacturer of seals or your local Endress+Hauser Sales Center. Height h for devices with flange...
  • Page 47 Version U1: material AISI 316L (1.4404), prepared for diaphragm seal mount Hole for filling fluid Bearing DIN 5401 (1.3505) Setscrew with hexagonal recess 4 mm (0.16 in), material A2-70 T14 housing T17 housing Height h 190 mm (7.48 in) 204 mm (8.03 in) Endress+Hauser...
  • Page 48: Pmp75 Basic Device

    • With the use of high-temperature oils the design can deviate strongly. • Observe the information in the "Planning instructions, diaphragm seal systems" section → ä 73 ff. • For further information please contact your local Endress+Hauser Sales Center. Endress+Hauser...
  • Page 49 3.50 (89) The specified nominal pressure applies to the diaphragm seal. The maximum pressure for the measuring device is dependent on the lowest-rated element, with regard to pressure, of the selected components. See also → ä 32, "Pressure specifications" section. Endress+Hauser...
  • Page 50 G 1 1/2 A Alloy C276 AISI 316L Alloy C276 AISI 316L 1 MNPT – Alloy C276 AISI 316L 1 1/2 MNPT 400 – Alloy C276 AISI 316L 2 MNPT – Alloy C276 28 mm (1.1 in) in conjunction with high-temperature oil Endress+Hauser...
  • Page 51 D [in] [mm] h [mm] L [mm] [kg] DN 25 PN 40 22.5 50.5 DN 38 1 1/2 PN 40 35.5 50.5 DN 51 PN 40 48.6 Including 3.1 and pressure test as per Pressure Equipment Directive, category II Endress+Hauser...
  • Page 52 ≤ 0.8 μm (31.5 μin) as stand- Process connection PMP75, surface roughness of the surfaces in contact with the media R ard. Lower surface roughness on request. Version Material Nominal Diaphragm seal weight pressure [kg] AISI 316L PN 25 0.75 Endress+Hauser...
  • Page 53 [inch] [bar] [mm] [mm] [mm] [mm] [mm] [kg] PN 40 1 13/16 – 1/8" 22 42.6 0.45 1 1/2 PN 40 2 5/16 – 1/8" 42.6 0.75 PN 40 2 7/8 – 1/8" 42.6 Endress+Hauser...
  • Page 54 [mm] [mm] [mm] [mm] [mm] [kg] DN 50 PN 25 68.5 Rd 78 x 1/6" DN 65 PN 25 Rd 95 x 1/6" DN 80 PN 25 Rd 110 x 1/4" 30 2.55 Endress+Hauser...
  • Page 55 The roughness of the surface in contact with the media, including the raised face of the flanges (all standards) made of Hastelloy C, Monel or tantalum, is Ra 0.8 μm (31.5 μin). Lower surface roughness on request. Designation as per DIN 2527 in brackets Endress+Hauser...
  • Page 56 (L) diameter d [mm] [mm] [kg] DN 50 PN 10-40 50 / 100 / 200 48.3 3.2 / 3.8 / 4.4 DN 80 PN 10-40 50 /100 / 200 6.2 / 6.7 / 7.8 Endress+Hauser...
  • Page 57 3.50 (89) 11.7 The roughness of the surface in contact with the media, including the raised face of the flanges (all standards) made of Alloy C, Monel or tantalum, is Ra 0.8 μm (31.5 μin). Lower surface roughness on request. Endress+Hauser...
  • Page 58 2 (50.8) / 4 (101.6) / 6 (152.4) / 8 (203.2) 3.7 (94) 8.6 / 9.9 / 11.2 / 12.4 2 (50.8) / 4 (101.6) / 6 (152.4) / 8 (203.2) 3.7 (94) 13.1 / 14.4 / 15.7 / 16.9 Endress+Hauser...
  • Page 59 The roughness of the surface in contact with the media, including the raised face of the flanges (all standards) made of Alloy C, Monel or tantalum, is Ra 0.8 μm (31.5 μin). Lower surface roughness on request. Housing weight → ä 63 Endress+Hauser...
  • Page 60 1/2 - 14 NPT G 1/2A P01-PMP75xxx-06-09-xx-xx-004 Process connection PMP75, versions "UA" and "UB", welded, material AISI 316L Version Description Nominal pressure Diaphragm seal weight [kg] ISO 228 G 1/2 A PN 160 1.43 ANSI 1/2 MNPT PN 160 1.43 Endress+Hauser...
  • Page 61 Process connection PMP75, versions "UC" and "UD", threaded, with integrated sealing lip Materials: AISI 316L (1.44.04), screws made of 1.4571 Version Measuring range Description Nominal pressure Diaphragm seal weight [kg] > 40 bar ISO 228 G 1/2 A PN 400 4.75 > 40 bar ANSI 1/2 MNPT PN 400 4.75 Endress+Hauser...
  • Page 62 T15 housing with display, high cover 215.5 mm (8.48 in) T17 housing, optional display on the side 213 mm (8.39 in) Endress+Hauser supplies these slotted nuts in stainless steel AISI 304 (DIN/EN material number 1.4301) or in AISI 304L (DIN/EN material number 1.4307). Endress+Hauser...
  • Page 63: Wall And Pipe Mounting With Mounting Bracket

    Process connections • Process connections PMC71 (with ceramic process isolating diaphragm): → ä 34 ff • Process connections PMP71 (with metallic process isolating diaphragm): → ä 41 ff • Process connections PMP75 (with diaphragm seal): → ä 48 ff Endress+Hauser...
  • Page 64: Material (Not Wetted)

    Blind plug PBT-GF30 FR, for dust ignition-proof: AISI 316L (1.4435) External operation (keys and key cover), Polycarbonate PC-FR, screw A4 RAL 7035 (gray) Devices with MID parts certificate Seal wire DIN 1367-0 St/Zn (soft galvanized steel) Seals Pb (lead) Endress+Hauser...
  • Page 65 Polyamide PA, for dust ignition-proof: CuZn nickel- plated Seal of cable gland and blind plug Silicone (VMQ) Blind plug PBT-GF30 FR, for dust ignition-proof: AISI 316L (1.4435) Devices with MID parts certificate Seal wire DIN 1367-0 St/Zn (soft galvanized steel) Seals Pb (lead) Endress+Hauser...
  • Page 66 UV-resistant Process connection adapter for AISI 316L (1.4404) separate housing Filling oil See "Ordering information" (→ ä 79) Miscellaneous: • Diaphragm seal capillary: AISI 316 Ti (1.4571) • Protective hose for diaphragm seal capillary: AISI 304 (1.4301) Endress+Hauser...
  • Page 67: Material (Wetted)

    • "Clamp connections" and "Hygienic connections" (see also "Ordering information" section): AISI 316L (DIN/EN material number 1.4435) • Endress+Hauser supplies process connections with threaded connections and DIN/ EN flanges made of stainless steel as per AISI 316L (DIN/EN material number 1.4404 (AISI 316) or 14435). With regard to their stability-temperature property, the materials 1.4404 and 1.4435 are grouped together under 13E0 in EN...
  • Page 68: Human Interface

    • Rapid and safe commissioning with the Quick Setup menus. Parameter Measured value display Identification Function name Value number Header line Main line Unit Information line Symbol – Bargraph Bargraph Editing modes Operating keys Selection options Value that can be edited Current measured value P01-xxxxxxxx-07-xx-xx-en-011 Endress+Hauser...
  • Page 69: Operating Elements

    /M-DAT DIP-switch for locking/unlocking DIP-switch for damping on/off DIP-switch for locking/unlocking parameters relevant to the measured values Green LED to indicate value being accepted parameters relevant to the measured values DIP-switch for simulation mode on/off DIP-switch for damping on/off Endress+Hauser...
  • Page 70: Local Operation

    Commubox FXA195 (see "Hardware and software for onsite and remote operation" section → ä 71 ff) • Field Xpert SFX100: Field Xpert is an industrial PDA with integrated 3.5" touchscreen from Endress+Hauser based on Windows Mobile. It communicates via wireless with the optional VIATOR Bluetooth modem connected to a HART device point-to-point or wireless via WiFi and Endress+Hauser’s Fieldgate FXA520.
  • Page 71: Hardware And Software For Onsite And Remote Operation

    /M-DAT can be ordered via feature 100 "Additional option 1" or feature 110 "Additional option 2" or as a spare part. → ä 79 ff. A CD with an Endress+Hauser operating program is also included in the scope of delivery.
  • Page 72 Connection options: • HART via Commubox FXA195 and the USB port on a computer • PROFIBUS PA via segment coupler and PROFIBUS interface card • Service interface with Commubox FXA291 and ToF adapter FXA291 (USB). For further information → www.endress.com Endress+Hauser...
  • Page 73: Planning Instructions, Diaphragm Seal Systems

    To help you select the right diaphragm seal system for your applications, Endress+Hauser provides its customers with the free "Applicator Sizing Diaphragm Seal" tool, which is available on CD or online at "www.endress.com/applicator".
  • Page 74 The volume change is the volume that has to be shifted to pass through the complete measuring range. Pressure transmitters from Endress+Hauser are optimized with regard to minimum volume change. Endress+Hauser...
  • Page 75: Diaphragm Seal Filling Oils

    Observe temperature limits of the device (→ ä 31) and the system (→ ä 73). Installation instructions Diaphragm seal systems • Endress+Hauser offer flushing rings as accessories to clean process isolating diaphragms without taking the transmitters out of the process. For further information please contact your local Endress+Hauser Sales Center.
  • Page 76 260 °C (500 °F). → Temperature application limits, see → ä 75, "Diaphragm seal filling oils" section. To minimize the influence of rising heat, Endress+Hauser recommends the device be mounted horizontally or with the housing pointing downwards.
  • Page 77: Certificates And Approvals

    Cerabar S Certificates and approvals CE mark The device meets the legal requirements of the relevant EC directives. Endress+Hauser confirms that the device has been successfully tested by applying the CE mark. Ex approvals • ATEX • FM • CSA •...
  • Page 78: Standards And Guidelines

    TC7975 North-American practice for Endress+Hauser instruments are designed according to ANSI/ISA 12.27.01 either as single seal or dual seal installation of process seals devices with annunciation, allowing the user to waive the use and save the cost of installing external secondary process seals in the conduit as required by the process sealing sections of ANSI/NFPA 70 (NEC) and CSA 22.1...
  • Page 79: Ordering Information

    400 mbar/40 kPa/6 psi g 8 bar/800 kPa/120 psi g 1 bar/100 kPa/15 psi g 10 bar/1 MPa/150 psi g 2 bar/200 kPa/30 psi g 18 bar/1.8 MPa/270 psi g 4 bar/400 kPa/60 psi g 25 bar/2.5 MPa/375 psi g Endress+Hauser...
  • Page 80 Thread ISO 228 G 2 A, Alloy C Thread ISO 228 G 2 A, Monel Thread ANSI 1 1/2 MNPT, AISI 316L (CRN) Thread ANSI 1 1/2 MNPT, Alloy C (CRN) Thread ANSI 1 1/2 MNPT, Monel (CRN) Thread ANSI 2 MNPT, AISI 316L (CRN) Endress+Hauser...
  • Page 81 Material test certificate for wetted components, inspection certificate as per EN 10204 3.1 acc. to specification 52005759 M Overvoltage protection Software setting, see additional spec. Min alarm current HART burst mode PV Min alarm current + HART burst mode PV HistoROM/M-DAT GL/ABS marine certificate NSF potable water approval Endress+Hauser...
  • Page 82 Overpressure test with certificate, inspection certificate as per EN 10204 3.1 Helium leak test EN 1518 with test certificate, inspection certificate as per EN 10204 3.1 Identification: Measuring point TAG, see additional specification Bus address, see additional specification PMC71 Order code Endress+Hauser...
  • Page 83: Pmp71

    T17 316L Hygiene IP66/68 NEMA6P; 7/8" plug, T17 = side cover Sensor range; Sensor over pressure limit (= OPL): Sensors for gauge pressure Measurement limits: –100 % (–1 bar) to +100 % of sensor nominal value Sensor rated value (URL) OPL (over pressure limit) Endress+Hauser...
  • Page 84 Thread DIN 13 M 20x1.5 EN 837 hole 11.4 mm, Alloy C Thread, flush-mounted process isolating diaphragm Thread ISO 228 G 1/2 A, DIN 3852, AISI 316L Thread ISO 228 G 1/2 A, DIN 3852, Alloy C Thread ISO 228 G 1 A, AISI 316L Endress+Hauser...
  • Page 85 Min alarm current + HART burst mode PV HistoROM/M-DAT GL/ABS marine certificate NSF potable water approval Test report acc. to EN10204 2.2 Routine test with certificate, inspection certificate as per EN 10204 3.1 Overpressure test with certificate, inspection certificate as per EN 10204 3.1 Endress+Hauser...
  • Page 86 Overpressure test with certificate, inspection certificate as per EN 10204 3.1 Helium leak test EN 1528 with test certificate, inspection certificate as per EN 10204 3.1 Identification: Measuring point TAG, see additional specification Bus address, see additional specification PMP71 Order code Endress+Hauser...
  • Page 87: Pmp75

    Sensor range; Sensor over pressure limit (= OPL): Sensors for gauge pressure Measurement limits: –100 % (–1 bar) to +100 % of sensor nominal value Sensor rated value (URL) OPL (over pressure limit) 400 mbar/40 kPa/6 psi 6 bar/600 kPa/90 psi Endress+Hauser...
  • Page 88 Tri-Clamp, ISO 2852 DN 38 (1 1/2"), DIN 32676 DN 40, AISI 316L (CRN), EHEDG Tri-Clamp, ISO 2852 DN 51 (2")/DN 50, AISI 316L (CRN), EHEDG Tri-Clamp, ISO 2852 DN 76.1 (3"), AISI 316L (CRN), EHEDG Pipe diaphragm seal Clamp connections Tri-Clamp, ISO 2852 DN 25 (1"), AISI 316L (CRN) Endress+Hauser...
  • Page 89 10K 50A RF, AISI 316L 10K 80A RF, AISI 316L 10K 100A RF, AISI 316L Other Thread ISO 228 G 1/2 A PN 160, separator, EN 837, welded, AISI 316L Thread ANSI 1/2 MNPT PN 160, separator, welded, AISI 316L (CRN) Endress+Hauser...
  • Page 90 Test report acc. to EN 10204 2.2 Routine test with certificate, inspection certificate as per EN 10204 3.1 Overpressure test with certificate, inspection certificate as per EN 10204 3.1 Identification: Measuring point TAG, see additional specification Bus address, see additional specification PMP75 Order code Endress+Hauser...
  • Page 91: Additional Documentation

    – 4 to 20 mA HART, – XA00253P Ex ia IIC T6 PMP75 PROFIBUS PA, FOUNDATION Fieldbus ATEX II 1 GD Ex ia IIC T6 PMC71, PMP71, – 4 to 20 mA HART, – XA00276P PMP75 PROFIBUS PA, FOUNDATION Fieldbus Endress+Hauser...
  • Page 92: Installation/Control Drawings

    – PROFIBUS PA, – XA00590P FOUNDATION Fieldbus FM/CSA IS + XP Class I PMP71, PMP75 – 4 to 20 mA HART – XA00592P + Division 1, Groups A – D – PROFIBUS PA, ZD00187P FOUNDATION Fieldbus – ZD00190P + XA00590P Endress+Hauser...
  • Page 93: Overfill Prevention

    CSA +XP Class I Division 1, PMP71, PMP75 – 4 to 20 mA HART – XA00599P Groups B - D, Class II – PROFIBUS PA, Division 1, Groups E - G, FOUNDATION Fieldbus Class III Overfill prevention • WHG: ZE00260P/00/DE Endress+Hauser...
  • Page 94: Configuration Data Sheet

    ❏ Main Value [%] ❏ Pressure ❏ Current [mA] (HART only) ❏ Temperature ❏ Level before lin. ❏ Tank content ❏ Error number ❏ Alternating display Depending on sensor and comunication variant Damping Damping: ___________ sec (Default 2 sec) Endress+Hauser...
  • Page 95: Pressure

    Main Value [%] ❏ Pressure ❏ Current [mA] (HART only) ❏ Temperature ❏ Error number ❏ Alternating display Depending on sensor and comunication variant Damping Damping: ___________ sec (Default 2 sec) Note! Smallest span (factory calibration) → ä 7. Endress+Hauser...
  • Page 96 Cerabar S Instruments International Endress+Hauser Instruments International AG Kaegenstrasse 2 4153 Reinach Switzerland Tel.+41 61 715 81 00 Fax+41 61 715 25 00 www.endress.com info@ii.endress.com TI00383P/00/EN/15.12 No 71185798 CSS/FM+SGML 9.0 71185798...