Lennox iComfort M30 Installation And Setup Manual page 21

Smart thermostat
Hide thumbs Also See for iComfort M30:
Table of Contents

Advertisement

Parameter Name
Feels Like
Wider Set Point Range
Heating Mode: Normal
or Comfort
Smart Away
Low Balance Point
High Balance Point
Deadband
Table 6. Parameter Descriptions
Definition
This feature will display the home temperature based on a combination of inputs. Feels Like uses outdoor
temperature, indoor temperature, and indoor humidity to determine the "feels like" condition of the home.
By default your thermostat operates within a range of 60-90°F. Enabling this options changes the range to
44-99°F.
Options are Normal and Comfort. Default is Normal. When changing to Comfort Mode, several parameters
are automatically modified for optimal system operations. The changed parameters are listed on the screen
when set to Comfort.
• Normal - This setting cools the home to the desired temperature setting. Once second-stage is activated
by timer or differential, it will not stage down to first-stage until the next heating cycle demand.
• Comfort - This is when the system could automatically stage up
or down based on the current load demand.
This setting when enabled controls the temperature in the home when no one is home. For this to function, the
Lennox Mobile app needs to be installed on a mobile device.
(Multistage Heat Pump Model only) -The default is 25°F. This option will only be available if an outdoor sensor
is installed. If the outside temperature is below the programmed Low Balance Point, then the compressor
stage operation is disallowed. This protects the compressor from operation and damage in cold outdoor tem-
peratures. Also, if the heat pump is not effective at a low outdoor temperature, then it is more comfortable and
efficient to go directly to the second stage. Low Balance Point can be disable in this screen. When this is
enable, the options are from –40°F to (the High Balance Point temperature -2) in 1.0°F steps.
The default is 50°F. This option is only available if an outdoor sensor is installed. If the outside temperature is
above the High Balance point, then the auxiliary heat stage is disallowed. This prevents the more expensive
auxiliary heat stage from operating, and forces the more efficient heat pump to satisfy the demand. High
Balance Point can be disable in this screen. When this is enable, the high balance point range is from (the low
balance point + 2) up to 75°F.
The deadband setting is the minimum difference between the cooling and heating setpoints. This setting is
used in auto-changeover to ensure smooth equipment operation. It also allows for flexibility of Humiditrol oper-
ation. The default deadband is 3 and the deadband is adjustable from 3 to 9°F degrees.
21

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents