Table 7-5 Status Tests - Honeywell UDC3300 Product Manual

Universal digital limit controller
Hide thumbs Also See for UDC3300:
Table of Contents

Advertisement

7.4
Status Tests,
Status Tests
Table 7-5
Status Tests
Test
Definition
(Lower
Display)
FAILSAFE
Failsafe Fault
RAM TEST
RAM Test Run
at
Power-up
CONF
Configuration
TEST
Checksum
CAL TEST
Working
Calibration
FACT CRC
Factory
Calibration Test
1/01
Continued
Table 7-5 lists the Status tests, the reason for their failure, and how to
correct the failure.
Upper
Reason for Failure
Display
NO
No Failure
YES
Burnout configured for none
and input fails.
–RAM TEST failed
–CONFTEST failed
–CALTEST failed
PASS
No Failure
FAIL
RAM Failure
PASS
No Failure
FAIL
Configuration data is in
error.
PASS
No Failure
FAIL
The working calibration
constants in the controller
are in error.
PASS
No Failure
FAIL
Factory set input constants
have been changed due to
the change in input type.
UDC3300 Limit Controller Product Manual
How to Correct the Failure
1. Step through the rest of the STATUS
check to identify the particular failure.
Also see Table 7-6, Background tests.
RAM test passed.
1. Power cycle to see if the error clears.
Configuration checksum passed.
1. Step through STATUS tests – the
controller will recalculate the
checksum.
2. Check all configuration prompts for
accuracy. See Section 3 -
Configuration.
Working calibration checksum passed.
1. If the controller has not been field
calibrated, see Section 3 -
Configuration and change the input to
a different type. Enter it, loop through
the status tests, then return the input
type to the original one.
2. If the controller has been field
calibrated, recalibrate the controller.
Factory calibration cyclic redundancy test
passed.
1. Cycle through Status to clear the error.
2. Check the calibration. Make sure 0 and
100% are correct values.
3. Recalibrate if step 1 is unsatisfactory.
Refer to Section 6 - Input Calibration.
75