Figure 2-6 Input #1 Connections - Honeywell UDC3300 Product Manual

Universal digital limit controller
Hide thumbs Also See for UDC3300:
Table of Contents

Advertisement

2.5
Wiring Diagrams,
Input #1 connections
Figure 2-6
Input #1 Connections
Thermocouple
Use Thermocouple
extension wire only
Remove screw and
install C/J on the "R" terminal,
connect tang to "–" terminals. 2
MV or Volts
except 0 –10 Volts
MV or Volt
source
+
1
The 250Ω load resistor for 4-20mA or the Voltage divider for 0–10 Volts or the 500 Ohm
C/J compensation resistor are supplied with the controller when the input is specified.
These items must be installed when you wire the controller before startup.
2 When installing the cold junction (Part number 30757088-001) for a T/C input, remove the screws from
terminals 25 and 27, and install the assembly into place.
14
Continued
Figure 2-6 shows the wiring connections for Input #1.
1
25
R
+
26
27
RTD
25
R
+
26
27
25
R
+
26
27