7.7
Troubleshooting Procedures,
Procedure #4
1/01
Table 7-11 explains how to troubleshoot a Keyboard failure.
Table 7-11
Troubleshooting a Keyboard Failure
Step
What to do
1
Make sure the keyboard is
connected properly to the
MCU/output and power/input
boards.
2
Controller Keyboard or specific keys
may be "LOCKED OUT" via the
security code.
3
Run the keyboard test.
4
Replace the display/keyboard if any
keys are shorted out.
UDC3300 Limit Controller Product Manual
Continued
How to do it
Withdraw the chassis from the case
and visually inspect the connection.
Use your 4 digit security code number
to change the lockout level. Refer to
Section 3 – Configuration.
ATTENTION
Using "1000" as a
security code number will override the
4-digit code previously entered.
Press the [SET UP] key and hold in,
then press the [FUNCTION] key at the
same time. The controller will run a
display test. Then you will see:
Upper Display
KEYS
Lower Display
TRY ALL
Press each key. If it works, the key
name will appear in the lower display.
Refer to "Replacement Procedures" in
this section.
Continued on next page