Lockout Data Set Up Group

Introduction
Lockout group
prompts
Table 4-1
Lockout Group Prompt Definitions
Lower Display
Prompt
SECURITY
LOCKOUT
34
The Lockout group provides three levels of keyboard security to protect
configuration and calibration data. To further secure the data, there is a
security code that can be entered which will permit changes to the lockout
configuration.
Table 4-1 lists all the function prompts in the "LOCKOUT" Set Up group
and their definitions.
Upper Display
Range of Setting
or Selection
0-4095
NONE
CALIB
+CONF
MAX
UDC3300 Limit Controller Product Manual
Parameter
Definition
SECURITY CODE—A security code may or may not be
used to protect configuration or keyboard Lockout
selection. In order to enable this feature, a code (up to
four-digits) between 1 and 4095 must be entered, then the
keyboard level lockout cannot be changed until you select
this number (or 1000 as an override). After selecting this
number here, be sure to copy and keep it in a secure
location.
NOTE: The Security Code is for keyboard entry only and is
not available via communications.
Can only be changed if "LOCKOUT" selection is "NONE."
LOCKOUT applies to one of the functional groups:
Configuration or Calibration. DO NOT CONFIGURE
UNTIL ALL CONFIGURATION IS COMPLETE.
No Lockout—all groups read/write.
CALIB—All are available for read/write except for the
Calibration group.
+CONF—All groups are read only.
MAX—Only Lockout group is available. No other
parameters are viewable.
1/01