Siemens SIMATIC ET 200SP Manual page 79

Fail-safe modul f-cm as-i safety st 3rk7136-6sc00-0bc1
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

"F-IN 1 ... 2" column
The "F-IN 1 ... 2" column shows the following information about the AS-i address via a color
code:
The numbers 1 to 2 designate the number of the input channel.
Gray
Green
White
Yellow
Red
"F-OUT 1 ... 4" column
The "F-OUT 1 ... 4" column shows the following information about the AS-i address via a
color code:
The numbers 1 to 4 designate the number of the output channel.
Gray
Green
White
Yellow
Red
If the output control is activated for the address, the F-CM AS-i Safety ST module can control
the status for F-OUT 1. The F-CM AS-i Safety ST module cannot control F-OUT 2 ... 4. The
value 0 is output here.
If an external control unit uses the output address, the dialog shows the statuses for
F-OUT 1 ... 4 read in on the AS-i bus.
Fail-safe Module F‑CM AS‑i Safety ST (3RK7136‑6SC00‑0BC1)
Manual, 03/2017, A5E03957059020A/RS-AB/002
7.1 Transferring code sequences via STEP 7 online access
The input channel is not present. A safe input slave was not detected
at the address.
The input channel shows the value 1 ("ON" status).
The input channel shows the value 0 ("OFF" status).
The input channel shows the value 0 ("OFF" state) or is not present.
Note:
The status indication is unambiguous once the code sequence has
been taught for a safe input slave (both inputs assigned with "ON"
signal), or when an "ON" signal has been read in for an externally
controlled safe output slave.
An error was detected, e.g., a code sequence error:
The status of the input channel cannot be read in. Substitute value 0 is
used.
The output channel is not present. A safe output channel was not
detected at the address.
The output channel shows the value 1 ("ON" status).
The output channel shows the value 0 ("OFF" status).
The output channel shows the value 0 ("OFF" state) or is not present.
Note:
The status indication is unambiguous once the code sequence has
been taught for a safe input slave (both inputs assigned with "ON"
signal), or when an "ON" signal has been read in for an externally
controlled safe output slave.
An error was detected, e.g., a code sequence error:
The status of the output channel cannot be read in.
Code sequences