Siemens SINAMICS G130 Engineering Manual page 394

Sinamics - low voltage sinamics drives
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

SINAMICS S120 Cabinet Modules
Engineering Information
Active Line Modules + Active Interface Modules
Active Infeeds must be regarded as requiring two separate auxiliary voltage supplies, i.e. one for the Active Interface
Module (AIM) and one for the Active Line Module (ALM).
The AIM requires the following voltages:
24 V DC:
Control electronics
230 V AC:
Cabinet ventilation, control voltage of precharging contactors depending on frame size
The ALM requires the following voltages:
24 V DC:
Control electronics
400 V resp. 690 V AC: Power unit fans
Active Interface Modules and Active Line Modules are delivered due to the required power connections as one unit.
For this reason, the auxiliary voltage connections of the AIM are already made to the auxiliary voltage supply system
of the ALM in the delivery state. Fuse protection down-circuit of the auxiliary voltage supply system is provided in the
Cabinet Modules.
The power requirement in the table below is based on the combination of Active Interface Module and Active Line
Module.
Order No.
Frame
size
Supply voltage 380 V – 480 V 3AC (DC link voltage 570 V – 720 V)
6SL3730-7TE32-1BA3
FX+FI
6SL3730-7TE32-6BA3
FX+FI
6SL3730-7TE33-8BA3
GX+GI
6SL3730-7TE35-0BA3
GX+GI
6SL3730-7TE36-1BA3
HX+HI
6SL3730-7TE38-4BA3
HX+HI
6SL3730-7TE41-0BA3
JX+JI
6SL3730-7TE41-0BC3
JX+JI
6SL3730-7TE41-4BA3
JX+JI
6SL3730-7TE41-4BC3
JX+JI
Supply voltage 500 V – 690 V 3AC (DC link voltage 750 V – 1035 V)
6SL3730-7TG35-8BA3
HX+HI
6SL3730-7TG37-4BA3
JX+JI
6SL3730-7TG37-4BC3
JX+JI
6SL3730-7TG41-0BA3
JX+JI
6SL3730-7TG41-0BC3
JX+JI
6SL3730-7TG41-3BA3
JX+JI
6SL3730-7TG41-3BC3
JX+JI
1)
Power requirement of control electronics, auxiliary power supply for fans.
SINAMICS Engineering Manual – November 2015
394/528
Ó Siemens AG
Rated rectifier/
Rated rectifier/
regenerative
regenerative
power at 400 V
current
or 690 V
I
rated
[kW]
[A]
132
210
160
260
235
380
300
490
380
605
500
840
630
985
630
985
900
1405
900
1405
630
575
800
735
800
735
1100
1025
1100
1025
1400
1270
1400
1270
1)
Current requirement
24 V
230 V AC
DC
50 Hz
60 Hz
[A]
[A]
1.27
0.6
1.27
0.6
1.52
1.2
1.52
1.2
1.57
4.6
1.57
4.6
1.67
4.9
1.67
4.9
1.67
4.9
1.67
4.9
1.57
4.6
1.67
4.9
1.67
4.9
1.87
4.9
1.87
4.9
1.87
4.9
1.87
4.9
400 V or 690V AC
50 Hz
60 Hz
[A]
[A]
[A]
0.9
0.63
0.9
0.9
1.13
1.6
1.8
1.8
2.7
1.8
1.8
2.7
6.8
3.6
5.4
6.8
3.6
5.4
7.3
5.4
8.0
7.3
5.4
8.0
7.3
5.4
8.0
7.3
5.4
8.0
6.8
2.1
3.1
7.3
3.1
4.6
7.3
3.1
4.6
7.3
3.1
4.6
7.3
3.1
4.6
7.3
3.1
4.6
7.3
3.1
4.6

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g150Sinamics s120Sinamics s150

Table of Contents