Maximum Connectable Motor Cable Lengths; Sinamics G150 Parallel Converters (Sinamics G150 Power Extension); Sinamics Engineering Manual – November - Siemens SINAMICS G130 Engineering Manual

Sinamics - low voltage sinamics drives
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

SINAMICS G150
Engineering Information
5.8.4

Maximum connectable motor cable lengths

The table below shows the maximum connectable motor cable lengths. The values apply to the motor cable types
recommended in the tables as well as to all other types of motor cable.
SINAMICS G150
Line supply voltage
400 V / 500 V / 690 V
Without reactor or filter
380 V – 480 V 3AC
500 V – 600 V 3AC
660 V – 690 V 3AC
With one motor reactor (option L08)
380 V – 480 V 3AC
500 V – 600 V 3AC
660 V – 690 V 3AC
With dv/dt filter plus VPL (option L10)
380 V – 480 V 3AC
500 V – 600 V 3AC
660 V – 690 V 3AC
With dv/dt filter compact plus VPL (option L07)
380 V – 480 V 3AC
500 V – 600 V 3AC
660 V – 690 V 3AC
With sine-wave filter (option L15)
380 V – 480 V 3AC
500 V – 600 V 3AC
Permissible motor cable lengths for SINAMICS G150
When two motor reactors are connected in series, the permissible cable lengths can be increased even further to
450 m with shielded cables and 675 m with unshielded cables. For SINAMICS G150 parallel converters with power
outputs ranging from 1750 kW to 2700 kW, the following values apply in the case of two motor reactors:
525 m for shielded cables and 787 m for unshielded cables.
A second motor reactor is not a standard option and may require an additional cabinet. A second motor reactor is
therefore available only on request.

5.9 SINAMICS G150 parallel converters (SINAMICS G150 power extension)

SINAMICS G150 cabinet units in the high output power range are designed as parallel converters. Their design is
based on either two lower-output SINAMICS G150 converter cabinet units or on two Basic Line Modules and two or
three Motor Modules.
Due to the design principle applied, each of the following components is used more than once in the configuration:
·
Line supply connections
·
Main contactors or circuit breakers
·
Power unit components
·
Motor connections
A parallel connection features only one each of the following:
·
CU320-2 Control Unit
·
AOP30 operator panel
·
Optional customer interfaces TM31 (option G60 or G61) or TB30 (option G62) with digital and analog
inputs and outputs
The following overview shows the three design variants of SINAMICS G150 parallel converters.
SINAMICS Engineering Manual – November 2015
324/528
Ó Siemens AG
Rated power at
e.g. Protodur NYCWY
110 kW - 900 kW
110 kW - 1000 kW
75 kW - 2700 kW
110 kW - 900 kW
110 kW - 1000 kW
75 kW - 2700 kW
110 kW - 900 kW
110 kW - 1000 kW
75 kW - 2700 kW
110 kW - 900 kW
110 kW - 1000 kW
75 kW - 2700 kW
110 kW - 250 kW
110 kW - 132 kW
Maximum permissible motor cable length
Shielded cable
300 m
300 m
300 m
300 m
300 m
300 m
300 m
300 m
300 m
100 m
100 m
100 m
300 m
300 m
Unshielded cable
e.g. Protodur NYY
450 m
450 m
450 m
450 m
450 m
450 m
450 m
450 m
450 m
150 m
150 m
150 m
450 m
450 m

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Sinamics g150Sinamics s120Sinamics s150

Table of Contents