Siemens SINAMICS G130 Engineering Manual page 288

Sinamics - low voltage sinamics drives
Hide thumbs Also See for SINAMICS G130:
Table of Contents

Advertisement

SINAMICS G130
Engineering Information
2.
The converter is controlled exclusively via the standard digital inputs/outputs on the Control Unit.
Terminal block on the CU320-2 Control Unit
-X122
Factory setting
DI0
ON/OFF 1
DI1
Increase setpoint/fixed setpoint 0
DI2
Decrease setpoint/fixed setpoint 1
DI3
Acknowledge fault
DI16
Not assigned
DI17
Not assigned
M1
M (GND)
DI/DO8
Inverter enable (Run)
DI/DO9
No fault
M (GND)
DI/DO10
P24
DI/DO11
External alarm
M (GND)
-X132
DI4
OFF 2
DI5
OFF 3
DI6
External fault 1
DI7
Not assigned
DI20
Not assigned
DI21
Not assigned
M2
M (GND)
DI/DO12
Error message acknowledgement, Braking
Module
DI/DO13
P24
M (GND)
DI/DO14
P24
DI/DO15
P24
M (GND)
The factory settings of the bidirectional inputs/outputs are underscored.
1)
A jumper must be inserted here if these inputs are not used
SINAMICS Engineering Manual – November 2015
288/528
Ó Siemens AG
1)
1)
1)
1)
Comment
Parameters can be set in the firmware to determine whether
operation is via motorized digital potentiometer or fixed
setpoint.
Factory-set as output
Low active
Immediate pulse disable, motor coasts to standstill
Ramp-down along quick-stop ramp, only of relevance in
conjunction with the Braking Module
Output is used (reserved) in conjunction with the Braking
Module
Factory-set as output
Factory-set as output
Factory-set as output