7.2.2.5

Cooling air requirements of air-cooled S120 Cabinet Modules

A specific quantity of cooling air must be supplied to air-cooled S120 Cabinet Modules. This volume of cooling air
must always be supplied, even under challenging boundary conditions. The cooling air is drawn in from the front
through the ventilation openings in the lower part of the cabinet doors. The heated air is expelled through the
perforated top cover or the ventilation openings in the top cover (with option M23/ M43/ M54). The minimum ceiling
height (for unhindered air outlet) specified in the dimension drawings must be observed. Cooling air can also be
supplied from below through raised floors or air ducts, for example. Openings in the 3-section baseplate must be
made for this purpose. Please also refer to the supplementary information for option M59 (Closed cabinet doors).
The tables below show the cooling air requirements of units in the Cabinet Modules range:
Line Connection Modules
Frame size
I
[A]
rated
Supply voltage 380 V to 480 V 3AC
FL
250
FL
380
GL
600
HL
770
JL
1000
JL
1250
JL
1600
KL
2000
KL
2500
LL
3200
Basic Line Modules
P
at 400 V
rated
Frame size
[kW]
Supply voltage 380 V to 480 V 3AC
FB
200
FB
250
FB
400
GB
560
GB
710
GD
900
Smart Line Modules
P
at 400 V
rated
Frame size
[kW]
Supply voltage 380 V to 480 V 3AC
GX
250
GX
355
HX
500
JX
630
JX
800
Active Line Module +
Active Interface Module
P
at 400 V
rated
Frame size
[kW]
Supply voltage 380 V to 480 V 3AC
FI+FX
132
FI+FX
160
GI+GX
235
GI+GX
300
HI+HX
380
HI+HX
500
JI+JX
630
JI+JX
900
1
Components use natural convection
2
Fan for degree of protection IP23, IP43, IP54 (in combination with Basic Line Modules)
Cooling air requirement
[m³/s]
1
-
1
-
1
-
1
-
1,2
0.36
1,2
0.36
1,2
0.36
1,2
0.72
1,2
0.72
1,2
0.72
Cooling air requirement
[m³/s]
0.17
0.17
0.17
0.36
0.36
0.36
Cooling air requirement
[m³/s]
0.36
0.36
0.78
1.08
1.08
Cooling air requirement
[m³/s]
0.47
0.47
0.83
0.83
1.18
1.18
1.48
1.48
SINAMICS S120 Cabinet Modules
Line Connection Modules
Frame size
I
[A]
rated
Supply voltage 500 V to 690 V 3AC
FL
280
FL
380
GL
600
HL
770
JL
1000
JL
1250
JL
1600
KL
2000
KL
2500
LL
3200
Basic Line Modules
P
at 690 V
rated
Frame size
[kW]
Supply voltage 500 V to 690 V 3AC
FB
250
FB
355
FB
560
GB
900
GB
1100
GD
1500
Smart Line Modules
P
at 690 V
rated
Frame size
[kW]
Supply voltage 500 V to 690 V 3AC
GX
450
HX
710
JX
1000
JX
1400
Active Line Module +
Active Interface Module
P
at 690 V
rated
Frame size
[kW]
Supply voltage 500 V to 690 V 3AC
HI+HX
630
JI+JX
800
JI+JX
1100
JI+JX
1400
SINAMICS Engineering Manual – November 2015
Engineering Information
Cooling air requirement
[m³/s]
1
-
1
-
1
-
1
-
1,2
0.36
1,2
0.36
1,2
0.36
1,2
0.72
1,2
0.72
1,2
0.72
Cooling air requirement
[m³/s]
0.17
0.17
0.17
0.36
0.36
0.36
Cooling air requirement
[m³/s]
0.36
0.78
1.08
1.08
Cooling air requirement
[m³/s]
1.18
1.48
1.48
1.48
389/528