IP 266
7.1.6 Example of a Complete Output Frame
The drive is to be moved backward - 35.750 mm in "relative increment mode"
(mode 7) at 20% of the incremental speed. BCD is to be used as data format.
The data formats recommended in Table 7-3 have been used in the table below
for the output frame.
Output frame:
Byte
KF
KH
Bit
7
0
+7
1
0/
1
2
0
4, 5
8003
6, 7
5750
The TOGGLE bit (bit 7) must change its value each time a command is issued. If it
was 0 for the last command, you must now enter a 1.
EWA 4NEB 812 6057-02
Communication Between the CPU and the IP 266
KM
Bit
Bit
Bit
Bit
Bit
Bit
6
5
4
3
2
1
0
0
0
1
0
0
Remarks
Bit
0
Mode 7
Bit 3:
REVERSE command
0
Bit 7:
TOGGLE bit
Not relevant in this mode
Relative distance - 35.750 mm
7-11