Emi And Environmental Type Tests - Siemens RUGGEDCOM RS401 Installation Manual

Hide thumbs Also See for RUGGEDCOM RS401:
Table of Contents

Advertisement

Chapter 6
Certification
Section 6.4

EMI and Environmental Type Tests

The RS401 has passed the following EMI and environmental tests.
IEC 61850-3 EMI Type Tests
Test
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-8
IEC 61000-4-29
IEC 61000-4-11
IEC 61000-4-12
IEC 61000-4-16
IEC 61000-4-17
IEC 60255-5
28
Description
ESD
Enclosure Contact
Radiated RFI
Enclosure ports
Burst (Fast Transient)
DC Power ports
AC Power ports
Earth ground ports
Surge
DC Power ports
AC Power ports
Induced
(Conducted) RFI
D.C Power ports
AC Power ports
Earth ground ports
Magnetic Field
Enclosure ports
Voltage Dips
DC Power ports
& Interrupts
AC Power ports
Damped Oscillatory
DC Power ports
AC Power ports
Mains Frequency
Voltage
DC Power ports
Ripple on DC
DC Power ports
Power Supply
Dielectric Strength
DC Power ports
AC Power ports
H.V. Impulse
Enclosure Air
Signal ports
Signal ports
+/- 4 kV line-to-earth, +/- 2 kV line-to-line
+/- 2 kV line-to-earth, +/- 1 kV line-to-line
+/- 4 kV line-to-earth, +/- 2 kV line-to-line
Signal ports
40 A/m continuous, 1000 A/m for 1 s
30% for 0.1 s, 60% for 0.1 s, 100% for 0.05 s
30% for 1 period, 60% for 50 periods
100% for 5 periods, 100% for 50 periods
Signal ports
2.5 kV common, 1 kV differential mode @ 1 MHz
2.5 kV common, 1 kV differential mode @ 1 MHz
2.5 kV common, 1 kV differential mode @ 1 MHz
Signal ports
Signal ports
Signal ports
Test Levels
+/- 8 kV
+/- 15 kV
20 V/m
+/- 4 kV @ 2.5 kHz
+/- 4 kV
+/- 4 kV
+/- 4 kV
10 V
10 V
10 V
10 V
30 V Continuous, 300 V for 1 s
30 V Continuous, 300 V for 1 s
10%
2 kVac  (Fail-Safe Relay output)
1.5 kVDC
2 kVAC
5 kV (Fail-Safe Relay output)
EMI and Environmental Type Tests
RUGGEDCOM RS401
Installation Guide
Severity
Levels
4
4
4
4
4
4
3
4
3
3
3
3
2
3
3
3
4
4
3

Advertisement

Table of Contents
loading