Grounding The Device; Cabling Recommendations - Siemens RUGGEDCOM RS401 Installation Manual

Hide thumbs Also See for RUGGEDCOM RS401:
Table of Contents

Advertisement

Chapter 2
Installing the Device
Figure 6: Failsafe Alarm Relay Wiring
1. Normally Open    2. Common    3. Normally Closed
Section 2.4

Grounding the Device

The RS401 chassis ground terminal uses a #6-32 screw. It is recommended to terminate the ground connection
with a #6 ring lug and torque it to 1.7 N·m (15 lbf·in).
Figure 7: Chassis Ground Connection
1. Stainless Steel Stud    2. #6-32 Screw    3. #6 Ring Lug
Section 2.5

Cabling Recommendations

All copper Ethernet ports on RUGGEDCOM products include transient suppression circuitry to protect against
damage from electrical transients and conform with IEC 61850-3 and IEEE 1613 Class 1 standards. This means
that during a transient electrical event, communications errors or interruptions may occur, but recovery is
automatic.
10
1
2
3
2
3
1
RUGGEDCOM RS401
Installation Guide
Grounding the Device