Installation Guide
Test
IEEE 1613 (C37.90.x) EMI Immunity Type Tests
NOTE
The RS401 meets Class 2 requirements for an all-fiber configuration and Class 1 requirements for
copper ports.
IEEE Test
C37.90.3
C37.90.2
C37.90.1
C37.90.1
C37.90
Environmental Type Tests
Test
IEC 60068-2-1
IEC 60068-2-2
IEC 60068-2-30
IEC 60255-21-1
IEC 60255-21-2
EMI and Environmental Type Tests
Description
IEEE 1613 Clause
9
8
Radiated RFI
7
Fast Transient
7
Oscillatory
6
Dielectric Strength
Cold Temperature
Dry Heat
Humidity (Damp Heat, Cyclic)
DC Power ports
AC Power ports
Description
ESD
Enclosure Contact
Enclosure Air
Enclosure ports
Signal ports
DC Power ports
AC Power ports
Earth ground ports
Signal ports
DC Power ports
AC Power ports
Signal ports
DC Power ports
AC Power ports
Description
Test Ad
Test Bd
Test Db
Vibration
Shock
Test Levels
5 kV
5 kV
Test Levels
+/- 8 kV
+/- 15 kV
35 V/m
+/- 4 kV @ 2.5 kHz
+/- 4 kV
+/- 4 kV
+/- 4 kV
2.5 kV common mode @ 1 MHz
2.5 kV common and
differential mode @ 1 MHz
2.5 kV common and
differential mode @ 1 MHz
2 kVAC
1.5 kVDC
2 kVAC
Test Levels
-40 °C (-40 °F), 16 Hours
85 °C (185 °F), 16 Hours
95% (non-condensing),
55 °C (131 °F), 6 cycles
2 g @ 10-150 Hz
30 g @ 11 ms