Siemens SIMATIC ET 200pro Manual page 40

Distributed i/o ethernet/ip interface module
Hide thumbs Also See for SIMATIC ET 200pro:
Table of Contents

Advertisement

The ET 200pro EtherNet/IP module
3.7 Device profile: supported CIP objects
Interface Control attribute
The Interface Control attribute is a structure consisting of Forced Interface Speed and
Control Bits.
If the autonegotiate bit is 0, the Forced Interface Speed bits indicate the speed at which the
interface operates. Speed is specified in megabits per second; for example, for 10 Mbps
EtherNet, the Interface Speed is 10. Interfaces not supporting the requested speed return
0x09 (Invalid Attribute Value). If autonegotiation is enabled, attempting to set the Forced
Interface Speed results in a response of 0x0C (Object State Conflict).
Control Bits operate as follows:
Bit(s)
0
1
Common services for EtherNet Link Object
Service
code
0x01
0x0E
0x10
40
Called:
Autonegotiate
Forced Duplex Mode
Need in implementation
Class
Instance
Optional
Optional
Conditional
Required
N/A
Conditional
Definition
0 = 802.3 link autonegotiation is disabled.
1 = autonegotiation is enabled.
If autonegotiation is disabled, the device uses the settings indicat-
ed by the Forced Duplex Mode and Forced Interface Speed bits.
If the Autonegotiate bit is 0, the Forced Duplex Mode bit indicates
whether the interface operates in full or half duplex mode.
0 = half duplex.
1 = full duplex.
Interfaces not supporting the requested duplex return 0x09 (Invalid
Attribute Value). If autonegotiation is enabled, attempting to set the
Forced Duplex Mode bits results in a response of 0x0C (Object
State Conflict).
Service name
Get_Attribute_All
Get_Attribute_Single
Set_Attribute_Single
ET 200pro distributed I/O EtherNet/IP interface module
Description
Supplies contents of all attrib-
utes.
Supplies contents of the appro-
priate attribute.
Modifies a single attribute.
Manual, 03/2016, A5E32861915-AB

Advertisement

Table of Contents
loading

Table of Contents