Extended Device Status - Bits 4-7
Bits 4-7
0 0 0 0
0 0 0 1
0 0 1 0
0 0 1 1
0 1 0 0
0 1 0 1
0 1 1 0
0 1 1 1
1 0 0 0
1 0 0 1
1 0 1 0 thru 1 1 1 1
Note
Behavior after a fault
A device may not be able to communicate in the Major Unrecoverable Fault state. Therefore,
it might not be able to report a Major Unrecoverable Fault. It will not process a Reset service.
The only exit from a Major Unrecoverable Fault is to cycle power.
Common services for Identity Object
Service code
0x0E
0x05
0x01
ET 200pro distributed I/O EtherNet/IP interface module
Manual, 03/2016, A5E32861915-AB
Extended Device Status Description
Self-testing or Unknown.
Firmware update in progress.
At least one faulted I/O connection.
No I/O connections established.
Nonvolatile configuration bad.
Major fault - either bit 10 or bit 11 is true (1).
At least one I/O connection in run mode.
At least one I/O connection established, all in idle mode.
Reserved, shall be 0.
Vendor/product specific.
Implemented for
Class
Instance
Yes
Yes
Yes
Yes
Yes
Yes
The ET 200pro EtherNet/IP module
3.7 Device profile: supported CIP objects
Service name
Get_Attribute_Single
Reset
Get_Attributes_All
31