5.5.3 Motor Control (Assigning Control Priority)

SIEMENS
3RW44
Menu
ESC
OK
1
Display mea-
1
sured value
select
ESC
OK
2
Status display
select
ESC
OK
3
Settings
select
ESC
OK
4
Motor
control
select
ESC
OK
1
Motor control
via keys
select
ESC
OK
2
Control motor
via inputs
select
ESC
OK
3
Standard
control
Inputs
change
ESC
OK
Figure 5-34:Motor control
SIRIUS 3RW44 System Manual
GWA 4NEB 535 2195-02 DS 04
Notice
The "Standard control" menu item specifies which control device should be the master
control device when the control supply voltage is applied.
When activating the PROFIBUS communication module, the setting is changed to
"Automatic/none".
Control device priority
Only a higher-priority control device can assume and hand over the control
priority (0 = lowest).
- 0:
Automatic operation (input control through PLC via PROFIBUS)
- 1:
PC via PROFIBUS (Soft Starter ES professional software required)
- 2:
Inputs
- 3:
Via display keys
- 4:
PC via serial interface (Soft Starter ES professional software required)
Possible values
Activate key control?
Deactivate key control?
Execute control functions
Activate "Control inputs"?
Deactivate "Control inputs"?
Automatic / none
Inputs
Keys
Commissioning
5-43