Siemens SIRIUS 3RW44 System Manual page 187

Soft starters
Hide thumbs Also See for SIRIUS 3RW44:
Table of Contents

Advertisement

ID
Bit
No
Byte
.
7
12
24
Temperature sensor monitoring
25 -26
Reserved = 0
15
28
Minimum current limit
16
29
Maximum current limit
30 - 31
Reserved = 0
0-5
32
Reserved = 0
6
14
32
Response to current limit value violation
7
32
Reserved = 0
0-1
33
Reserved = 0
2
140 33
Response to overload - contact block
4-7
33
Reserved = 0
0-2
21
34
Asymmetric limit value
3-5
34
Reserved = 0
6
20
34
Response to asymmetry
7
22
34
Response to ground fault
35 - 44
Reserved = 0
47
45
Braking torque
46 - 47
Reserved = 0
40
48
Start voltage
49
Reserved = 0
42
50
Current limit value
0-3
167 51
Starting mode
SIRIUS 3RW44 System Manual
GWA 4NEB 535 2195-02 DS 04
Meaning
PROFIBUS DP Communication Module
Only
for
data
Value range [coding]
set
131
x
• No [0]
• Yes [1]
18.75 ... 100 % [6 ... 32]
50 ... 150 % [16 ... 48]
x
• Warning [0]
• Tripping [1]
x
• Tripping without
restart [0]
• Tripping with restart [1]
x
30 ... 60 % [3 ... 6]
x
• Warning [0]
• Tripping [1]
x
• Warning [0]
• Tripping [1]
20 ... 100 % [4 ... 20]
20 ... 100 % [4 ... 20]
• 3RW44 2, 3, 4:
125 ... 550 % [40 ... 176]
• 3RW44 5:
125 ... 500 % [40 ... 160]
• 3RW44 6:
125 ... 450 % [40 ... 144]
• Direct on line [0]
• Voltage ramp [1]
• Torque control [2]
• Motor heating [3]
• Voltage ramp + current limiting
[5]
• Torque control + current limiting
[6]
Factor
3.125 %
3.125 %
10 %
5 %
5 %
3.125 %
8-63

Advertisement