Data Set 92 - Reading The Device Diagnosis - Siemens SIRIUS 3RW44 System Manual

Soft starters
Hide thumbs Also See for SIRIUS 3RW44:
Table of Contents

Advertisement

8.12.9 Data Set 92 - Reading the Device Diagnosis

ID
Bit
Byte
No.:
Switching/controlling:
0
301
0
Ready (automatic)
1
306
0
Motor right
2
307
0
Motor left
3
309
0
Contact block overload
4
308
0
Contact block damaged
5
310
0
Emergency start is active
6
302
0
Group error
7
304
0
Group warning
0
1
Reserved = 0
1
319
1
No main power
2
1
Reserved = 0
3
312
1
Start mode active
4
313
1
Stopping mode active
5
1
Reserved = 0
6
316
1
Electrical braking procedure is
active
7
314
1
Slow speed active
Protective function: Motor/line/short-circuit
0
324
2
Temperature sensor overload
1
325
2
Temperature sensor open
2
326
2
Temperature sensor short
SIRIUS 3RW44 System Manual
GWA 4NEB 535 2195-02 DS 04
Signal bit
PROFIBUS DP Communication Module
E
Meaning/Acknowledgment
*)
No.
Device ready for operation via host (e.g. PLC),
The signal bit is updated continuously.
Contact block 1 switched on.
The signal bit is updated continuously.
Contact block 2 switched on.
The signal bit is updated continuously.
E5,
For example, power semiconductor too hot, causing the
E24
motor to switch off.
The signal bit is deleted when the cause for the switch-off
has been remedied and acknowledged via "Trip reset".
E9
For example, contactor welded/blocked or power
semiconductor has become short-circuited.
The signal bit can only be deleted by switching the supply
voltage on / off when the cause of error is remedied.
The signal bit is deleted when the emergency start is
deactivated.
At least one error is set which generates an error
number.
The signal bit is deleted when the cause for the switch-off
has been remedied and acknowledged via "Trip reset",
autoreset or OFF command.
At least one warning is pending.
The signal bit is updated continuously.
E17,
The signal bit is deleted when the cause for the switch-
E24
off has been remedied and acknowledged via "Trip
reset".
The signal bit is updated continuously.
The braking output is switched on by the soft starter.
The signal bit is updated continuously.
The signal bit is updated continuously.
E4
Overload recognized, the signal bit is updated
continuously.
E6
The thermistor circuit has been interrupted.
The signal bit is updated continuously.
E1
Short circuit in the thermistor circuit.
The signal bit is updated continuously.