Soft Starter With Contactor Disconnector (Main Contactor) - Siemens SIRIUS 3RW44 System Manual

Soft starters
Hide thumbs Also See for SIRIUS 3RW44:
Table of Contents

Advertisement

Installation, Connection and Branch Layout

3.2.4 Soft starter with Contactor Disconnector (Main Contactor)

3-8
If galvanic decoupling is required, a motor contactor can be installed between
the soft starter and the disconnector, or a fault output relay can be used.
(Refer to Chapter 10.3 "Technical Data" for the contactor assignment)
3/N/PE~ 50 Hz 400 V
L1
L2
L3
PE
Q11
U1
V1
W1
W2
U2
V2
Figure 3-6:Block diagram of branch with optional main contactor / contactor disconnector
Notice
If a main or line contactor is used, this contactor must not be connected
between the soft starter and the motor or in the return line between the motor
and the soft starter. Otherwise the soft starter would not recognize the current
circuit version (standard circuit or inside delta circuit) and would output the error
message: "Load phases 1-3 missing".