Configuration Instructions

2.2.3 Application Examples for Very Heavy Starting (CLASS 30)

Very heavy starting CLASS 30 (up to 60 s with 350 % I
The selected soft starter must have a power class that is 2 classes higher than that of the implemented motor
Application
Starting parameters
• Voltage ramp and current
limiting
- Start voltage
- Starting time
- Current limit value
• Torque ramp
- Start torque
- End torque
- Starting time
• Breakaway pulse
Stopping mode
2-4
),
n motor
Large fans
%
30
s
60
4 x I
M
20
150
60
Deactivated (0 ms)
Coasting down
Note
These tables provide example set values and device dimensionings. They serve
as information only and are not binding. The set values are application-
dependent and must be optimized during commissioning.
Soft starter dimensioning should, if necessary, be verified with the help of the
Win-Soft Starter program or via the Technical Assistance in Chapter "Important
notes".
Mills
Crushers
50
50
60
60
4 x I
4 x I
M
50
50
150
150
60
60
80 %; 300 ms
80 %; 300 ms
Coasting down
Coasting down
Disk saws/ribbon saws
30
60
4 x I
M
M
20
150
60
Deactivated (0 ms)
Coasting down