• CP1W-32ER's maximum number of simultaneously ON output points is 24 (75%).
Relation between Number of ON Outputs and
Ambient Temperature (CP1W-32ER)
Number of inputs ON
simultaneously (%)
According to the ambient temperature, there are restrictions on power supply voltage and output load
current for the CPU Units connected with the Expansion I/O Units (CP1W-8ER/16ER/20EDR1/
32ER/40EDR). Use the PLC in the range of the power supply voltage and output load current as show
below.
• The ambient temperature is restricted for the CPU Units (CP1E-N/NA
Derating curve of the output load current for Expansion I/O Units (CP1W-8ER/16ER/20EDR1/
32ER/40EDR).
Connected to
CP1E-N30DR-D
100%
Power voltage:
21.6 VDC
50%
Power voltage:
20.4 VDC
0%
55 °C
35
45
Ambient temperature
Connected to
CP1E-N60DR-D
CP1E-N60 DT -D
100%
Power voltage:
21.6VDC
50%
Power voltage:
20.4VDC
0%
40 45
55˚C
Ambient temperature
CP1E CPU Unit Hardware User's Manual(W479)
75
0
55
Ambient temperature (˚C)
Connected to
CP1E-N40DR-D
100%
Power
voltage:
21.6 VDC
50%
Power
voltage:
20.4 VDC
0%
55 °C
30
45
50
Ambient temperature
Connected to
CP1E-NA20DT -D
100%
Power voltage:
21.6VDC
50%
Power voltage:
20.4VDC
0%
40 45
55˚C
Ambient temperature
3 Part Names and Functions
Connected to
CP1E-N30 DT -D
100%
Power voltage:
21.6 VDC
50%
Power voltage:
20.4 VDC
0%
55 °C
35
45
Ambient temperature
Connected to
CP1E-NA20DR-A
100%
80%
0%
50
55˚C
Ambient temperature
D - ).
Connected to
CP1E-N40 DT -D
100%
Power
voltage:
21.6 VDC
50%
Power
voltage:
20.4 VDC
0%
55 °C
35
45
Ambient temperature