Omron CP1E-E14SDR-A User Manual page 126

Sysmac cp series cp1e series cpu unit hardware
Table of Contents

Advertisement

Using Wiring Ducts
Whenever possible, route I/O wiring through wiring ducts. Install the ducts so that it is easy to wire the
I/O Units through the ducts. It is handy to have the ducts at the same height as the Racks. Use mount-
ing bases if necessary to adjust the heights.
Duct
20mm min.
DIN Track
Unit
20mm min.
Duct
Precautions for Correct Use
Precautions for Correct Use
Tighten terminal block screws and cable screws to the following torques.
M4: 1.2 N·m
M3: 0.5 N·m
Routing Wiring Ducts
Install the wiring ducts at least 20 mm between the tops of the Racks and any other objects, (e.g.,
ceiling, wiring ducts, structural supports, devices, etc.) to provide enough space for air circulation
and replacement of Units.
Input duct
CP1E
Fuses, timers,
relays, etc.
(Not heat-
generating
equipment or
power
equipment.)
CP1E CPU Unit Hardware User's Manual(W479)
30mm
40mm
Output duct
Power duct
200 mm min.
Breaker
Fuse
Power
equipment,
such as
transformers
and magnetic
relays
Terminal
Terminal blocks
blocks for
for power
PLC
equipment
5 Installation and Wiring
81.6~89.0mm
CPU
Rack
30mm
Mounting bracket
Duct
5
5-11

Hide quick links: