8 Using Expansion Units and Expansion I/O Units
Additional Information
• Unused bits in the CompoBus/S I/O Link Unit's output words can be used as work bits.
• Unused bits in input word cannot be used as work bits.
2
Determine the node number and make DIP switch settings.
(1) Determining Node Number
• The CompoBus/S I/O Link Unit is a Slave Unit with 8 input bits and 8 output bits. The
node number setting is made using the DIP switch; the inputs and outputs share the
same node number.
• The range of possible node number settings is determined by the type of PLC the Master
Unit is mounted to and the settings on the Master Unit.
For details, refer to the CompoBus/S Operation Manual (Cat. No. W266).
(2) Making DIP Switch Settings
Use the DIP switch to set the CompoBus/S I/O Link Unit's node number, communications
mode, and the status of output data when a communications error occurs.
Precautions for Correct Use
Precautions for Correct Use
Always turn OFF the power supply before changing the DIP switch settings.
3
Wire the CompoBus/S communications path.
BD L
BD L
BD H
8-56
These terminals are not used. They can
however be used as communications power
BD H NC (BS+)
supply relay terminals.
NC (BS−)
NC
Connect the CompoBus/S Communications Cable.
CP1E CPU Unit Hardware User's Manual(W479)