Communication Services And Used Port Numbers - Siemens SINAMICS Configuration Manual

Industrial security, medium-voltage converter
Hide thumbs Also See for SINAMICS:
Table of Contents

Advertisement

Risk of death due to software manipulation when using exchangeable storage media
Storing the parameterization (incl. Safety Integrated parameterization) on exchangeable
storage media carries the risk that the original parameterization (with Safety Integrated) will
be overwritten, for example, by the memory card of another drive without Safety Integrated.
Incorrect parameter assignment can cause machines to malfunction, which can lead to
injuries or death.
● Ensure that only the memory card that belongs to the respective inverter is used.
● Ensure that only trained or authorized personnel have access to the enclosures, cabinets
5.5

Communication services and used port numbers

SINAMICS converters support the communication protocols listed in the following table. The
address parameters, the relevant communication layer, as well as the communication role and
the communication direction are decisive for each protocol. You require this information to
match the security measures for the protection of the automation system to the used protocols
(e.g. firewall). The security measures are restricted to Ethernet and PROFINET networks.
The following table shows the various layers and protocols that are used.
Layers and protocols
Report
PROFINET protocols
DCP
Discovery and
configuration pro‐
tocol
LLDP
Link Layer Dis‐
covery protocol
Industrial Security
Configuration Manual, 08/2017, A5E36912609A
WARNING
or electrical equipment rooms.
Port number (2) Link layer
Not relevant (2) Ethernet II and
Not relevant (2) Ethernet II and
5.5 Communication services and used port numbers
Function
(4) Transport layer
Accessible no‐
IEEE 802.1Q and
des,
Ethertype 0x8892
PROFINET
(PROFINET)
Discovery and
configuration
PROFINET
IEEE 802.1Q and
Link Layer Dis‐
Ethertype 0x88CC
covery protocol
(PROFINET)
Security measures for SINAMICS
Description
DCP is used by PROFI‐
NET to determine PRO‐
FINET devices and to
make basic settings.
DCP uses the special
multicast MAC address:
xx-xx-xx-01-0E-CF,
xx-xx-xx = Organization‐
ally Unique Identifier
LLDP is used by PROFI‐
NET to determine and
manage neighborhood
relationships between
PROFINET devices.
LLDP uses the special
multicast MAC address:
01-80-C2-00-00-0E