5 Drives Configuration
To adjust Drive Object Number order, Highlight Drive Object and then use Up and
Down arrows to move Position ("-No." field).
Figure 5-3
5.3

Set to EIP Communication

1. Open expert List for CU and Set P2030 to [10] Ethernet/IP. This works the
same for the CU310-2 PN as well.
Figure 5-4
2. Project Offline commissioning should be completed at this time. Highlight CU
and Go Online with Starter. Download offline project to Control Unit. After
Downloading and Saving Ram to ROM (this is usually default with download)
the communication for the S120 is now ready.
Power Cycle S120 and then EIP will take effect on Power Up.
Figure 5-5
SINAMICS S: Speed control of a S120 with an Allen-Bradley controller
(Compact/ ControlLogix with RSLogix 5000) via EtherNet/IP