Advertisement

Communication
A.1 Communication
PROFIBUS is tuned for high-speed, time-critical data communication at field level.
Note
PROFIBUS for drive technology is standardized and described in the following document:
PROFIdrive Profile Drive Technology
PROFIBUS User Organization e. V.
Haid-und-Neu-Strasse 7, D-76131 Karlsruhe
Internet: (http://www.profibus.com)
Note
Before synchronizing to the isochronous PROFIBUS, all of the drive object pulses must be
inhibited - also for those drives that are not controlled via PROFIBUS.
PROFIBUS interface: The cyclic PZD channel is deactivated when the CBE20 is plugged in!
NOTICE
Destruction of the CU320‑2 or other CAN bus nodes by connecting a CAN cable
Connecting a CAN cable to interface X126 of the CU320-2 can destroy the CU320‑2 or other
CAN bus nodes.
● Do not connect any CAN cable to the X126 interface.
Master and slave
● Master and slave properties
● Master
The following classes are differentiated:
– Master class 1 (DPMC1):
– Master class 2 (DPMC2):
● Slaves
With respect to PROFIBUS, the SINAMICS drive unit is a slave.
114
Properties
As bus node
Send messages
Receive messages
Central automation stations that exchange data with the slaves in cyclic and acyclic
mode. Communication between the masters is also possible.
Examples: SIMATIC S7, SIMOTION
Devices for configuration, commissioning, operator control and monitoring during bus
operation. Devices that only exchange data with the slaves in acyclic mode.
Examples: Programming devices, human machine interfaces
Master
Active
Permitted without external re‐
quest
Possible without any restric‐
tions
Configuration Manual, 08/2017, A5E36912609A
Slave
Passive
Only possible on request by
master
Only receive and acknowledge
permitted
Industrial Security