C. Hearth Pad Requirements (UL and ULC)
Use a non-combustible floor protector, extending beneath
appliance and to the front, sides and rear as indicated.
Measure front distance "M" from the surface of the glass
door.
K
Figure 9.1
Hearth Pad Requirements
K
Sides
L*
Back
M
Front
*L Exception for Horizontal Installations:
USA INSTALLATIONS: A non-combustible floor protec-
tion is recommended extending beneath the flue pipe
when installed with horizontal venting or under the top
vent adapter with vertical installation.
CANADA INSTALLATIONS:
protection extending beneath the flue pipe is required
with horizontal venting or under the top vent adapter with
vertical installation.
Must extend 2 inches (51mm) beyond each
side of pipe (shaded area)
Figure 9.2
September 1, 2008
L*
K
M
Inches
Millimeters
2
51
2
51
6
152
A non-combustible floor
7014-082D
CB 1200 Pellet Stove
Page 9