SANTA FE FREESTANDING
C. Hearth Pad Requirements (UL and ULC)
EMBER PROTECTION: It is necessary to install a Type I
floor protector.
Floor protector must be non-combustible material,
extending beneath appliance with a minimum of 6 inches
(152mm) in front of glass and 6 inches (152mm) to both
sides of the fuel loading door. Open the door and measure
6 inches (152mm) from the side edge of the opening in the
face of the appliance.*See exception.
27 in
minimum
FUEL DOOR OPENING
6 in
6 in
from the fuel door
opening
USA
15 in
Figure 11.1
Must extend 51mm
beyond each side
of pipe (shaded area)
to the wall thimble.
152MM
CANADA
Figure 11.2
11
6 in
686mm
minimum
FUEL DOOR OPENING
152MM
152MM
FROM FUEL DOOR
OPENING
USA INSTALLATIONS: A non-combustible floor protection
is recommended extending beneath the flue pipe when
installed with horizontal venting or under the Top Vent
Adapter with vertical installation.
CANADA INSTALLATIONS: A non-combustible floor
protection extending beneath the flue pipe is required
with horizontal venting or under the Top Vent Adapter with
vertical installation.
26-1/2 in
minimum
32-1/4 in
Figure 11.3
673mm
minimum
819mm
Figure 11.4
7050-801E
WARNING
Fire Risk
Comply with all minimum clearances to
combustibles as specified.
Failure to comply may cause house fire.
1006mm
Must extend 51mm
beyond each side
of pipe (shaded area)
to the wall thimble.
381mm
39-5/8 in
22-3/4 in
15 in
USA
578mm
CANADA
09/20