Setting acceleration/deceleration time (,) in conformance with mean load allows optimum
setting that conforms to further changes in load.
Use this parameter after actually connecting the motor.
When the inverter is used with a load that fluctuates considerably, it may fail to adjust the acceleration or
deceleration time in time, and therefore may be tripped.
Do not use = when using a brake module (optional).
[Methods of setting automatic acceleration/deceleration]
Operation panel
5
5.3.2
Set acceleration time from 0.0 (Hz) operation frequency to maximum frequency and deceleration time as
the time when operation frequency goes from maximum frequency to 0.0 (Hz).
Output frequency (Hz)
[Parameter setting]
Note: When the acceleration/deceleration time is set to 0.0 seconds, the inverter accelerates and decelerates
LED display
action
MODE
⇔
Manually setting acceleration/deceleration time
O
Title
Function
Acceleration time 1
Deceleration time 1
0.05 seconds.
Displays the operation frequency.
(When standard monitor display selection is set to
[Operation frequency])
The first basic parameter "" (history function) is displayed.
Turn the setting dial to the right to change the parameter to .
Parameter values can be read by pressing the center of the setting
dial.
Turn the setting dial to the right to change the parameter to or .
Press the center of the setting dial to save the changed parameter.
and the parameter are displayed alternately.
Time [sec]
Adjustment range
0.0-3000 sec.
0.0-3000 sec.
E-6
E6581595
Operation
= (Manual)
Default setting
10.0
10.0