Panasonic S-200PE2E5 Technical Data & Service Manual page 39

Dc inverters
Table of Contents

Advertisement

OUTDOOR UNIT/3-PHASE MODEL
This equipment complies with EN/IEC 61000-3-12 provided that the short-circuit power Ssc is greater than or equals to 1850 kVA at
the interface point between the user's supply and the public system. It is the responsibility of the installer or user of the equipment
to ensure; by consultation with the distribution network operator if necessary that the equipment is connected only to supply with a
short-circuit power Ssc greater than or equals to 1850 kVA.
Ssc : Short circuit power
SG : Shows the ground for the shielded cable.
Model name
U-200PE2E8A
U-250PE2E8A
*
1 Use a shielded cable for the control cable. Overall extension less than 1000m.
Decide the length and size of the power supply cable based on the maximum ampere tabulated above in accordance with the
national wiring regulations.
Select the fuse(s) and/or circuit breaker(s) from the types and ratings suitable for the maximum ampere tabulated above in
accordance with the national wiring regulations.
If capacity of power supply circuit and enforcement are not enough, it can causes the electric shock and a fi re.
For the shield part of the shielded cable, twist the end out, crimp it with a
round terminal, and connect it to the SG screw.
After crimping it with a round terminal, wrap it with insulating tape so there
are no spaces and adjust it so the shield part does not touch any live parts.
Be sure that the shield part of the shielded cable does
CAUTION
not touch the terminal block or any live parts.
Failure to do so may lead to electric shock or fi re.
Indoor Unit 4-Way Cassette
Earth
Earth
L
L
N
N
Controll
cable
U1
U1
U2
U2
R1
R1
R2
R2
Indoor unit
Indoor unit
(TRIPLE type)
(DOUBLE TWIN type)
SG : Shows the earth for the shielded cable.
AMP Air Conditioning
Power supply (220/230/240V~)
C
c r i
i u
b t
e r
k a
r e
Switch
Earth
L
N
Control cable
SG
U1
U2
R1
R2
2
1
Wired remote
Indoor unit
controller
Maximum electric
Power supply
current
380/400/415V 3N~
380/400/415V 3N~
Circuit breaker
Earth
Earth
L
L
N
N
Controll
Controll
cable
cable
U1
U1
U2
U2
R1
R1
R2
R2
Indoor unit
Indoor unit
Power supply (380/400/415V 3N~)
C
c r i
i u
b t
e r
k a
r e
Switch
L1
L2
L3
N
Earth
SG
U1
U2
Outdoor unit
*
1
Control cable
0.75 mm ²
20 A
0.75 mm ²
20 A
Crimp the round terminal
Shield part
Power supply
Power supply
(380/400/415V 3N~)
(220/230/240V~)
Circuit breaker
Switch
Switch
L1
L2
Controll
L3
cable
N
Earth
U1
U2
Wired remote
Outdoor unit
controller
1-33
www.ampair.co.uk | sales@ampair.co.uk
Ssc
1850 kVA
1850 kVA
Wrap it well with insulating
tape so there are no spaces.
1