1
4-Way Cassette Type
1. Cooling Capacity Performance Data
Model
Source
220V/230V/240V
S-100PU2E5A×2
50Hz 1phase
U-200PE2E8A
(380V/400V/415V
50Hz 3 phase)
220V/230V/240V
S-125PU2E5A×2
50Hz 1phase
U-250PE2R8A
(380V/400V/415V
50Hz 3 phase)
2. Heating Capacity Performance Data
Model
Source
220V/230V/240V
S-100PU2E5A×2
50Hz 1phase
U-200PE2E8A
(380V/400V/415V
50Hz 3 phase)
220V/230V/240V
S-125PU2E5A×2
50Hz 1phase
U-250PE2E8A
(380V/400V/415V
50Hz 3 phase)
AMP Air Conditioning
Ambient
Power
Return
Air
DB
WB
TC
16
24.5 19.1 6.71 22.2 18.1 8.20 20.6 17.4 8.04 18.6 16.5 7.63 17.2 15.8 7.05
23
19
26.3 14.3 6.87 24.0 13.4 8.36 22.4 12.8 8.20 20.4 12.0 7.79 19.0 11.5 7.22
22
28.0
16
24.5 21.9 6.71 22.2 20.8 8.20 20.6 20.1 8.04 18.6 18.6 7.63 17.2 17.2 7.05
25
19
26.3 17.1 6.87 24.0 16.2 8.36 22.4 15.6 8.20 20.4 14.8 7.79 19.0 14.3 7.22
22
28.0 12.4 7.04 25.8 11.6 8.53 24.2 11.0 8.36 22.2 10.3 7.95 20.8
16
24.5 24.4 6.71 22.2 22.1 8.20 20.6 20.5 8.04 18.6 18.6 7.63 17.2 17.2 7.05
27
19
26.3 19.9 6.87 24.0 19.0 8.36 22.4 18.3 8.20 20.4 17.5 7.79 19.0 17.0 7.22
22
28.0 15.1 7.04 25.8 14.3 8.53 24.2 13.7 8.36 22.2 13.0 7.95 20.8 12.6 7.38
16
24.5 24.4 6.71 22.2 22.2 8.20 20.6 20.6 8.04 18.6 18.6 7.63 17.2 17.2 7.05
29
19
26.3 22.7 6.87 24.0 21.8 8.36 22.4 21.1 8.20 20.4 20.4 7.79 19.0 19.0 7.22
22
28.0 17.9 7.04 25.8 17.1 8.53 24.2 16.5 8.36 22.2 15.8 7.95 20.8 15.3 7.38
16
24.5 24.5 6.71 22.2 22.1 8.20 20.6 20.5 8.04 18.6 18.6 7.63 17.2 17.2 7.05
32
19
26.3 26.3 6.87 24.0 24.0 8.36 22.4 22.4 8.20 20.4 20.4 7.79 19.0 19.0 7.22
22
28.0 21.9 7.04 25.8 21.1 8.53 24.2 20.6 8.36 22.2 19.9 7.95 20.8 19.4 7.38
16
30.6 22.3 9.33 27.7 20.9 11.4 25.8 20.0 11.2 23.2 18.8 10.6 21.6 18.1 9.81
23
19
32.8 17.3 9.56 30.0 16.1 11.6 28.0 15.2 11.4 25.5 14.2 10.8 23.8 13.5 10.0
22
35.1 12.3 9.79 32.2 11.2 11.9 30.2 10.5 11.6 27.7
16
30.6 25.2 9.33 27.7 23.8 11.4 25.8 22.9 11.2 23.2 21.6 10.6 21.6 21.0 9.81
25
19
32.8 20.2 9.56 30.0 18.9 11.6 28.0 18.1 11.4 25.5 17.1 10.8 23.8 16.3 10.0
22
35.1 15.2 9.79 32.2 14.1 11.9 30.2 13.3 11.6 27.7 12.3 11.1 26.0 11.7 10.3
16
30.6 28.1 9.33 27.7 26.7 11.4 25.8 25.8 11.2 23.2 23.2 10.6 21.6 21.6 9.81
27
19
32.8 23.1 9.56 30.0 21.8 11.6 28.0 20.9 11.4 25.5 19.9 10.8 23.8 19.2 10.0
22
35.1 18.0 9.79 32.2 16.9 11.9 30.2 16.1 11.6 27.7 15.1 11.1 26.0 14.6 10.3
16
30.6 30.7 9.33 27.7 27.6 11.4 25.8 25.7 11.2 23.2 23.1 10.6 21.6 21.6 9.81
29
19
32.8 26.0 9.56 30.0 24.6 11.6 28.0 23.8 11.4 25.5 22.8 10.8 23.8 22.0 10.0
22
35.1 20.8 9.79 32.2 19.7 11.9 30.2 19.0 11.6 27.7 18.0 11.1 26.0 17.3 10.3
16
30.6 30.5 9.33 27.7 27.7 11.4 25.8 25.8 11.2 23.2 23.2 10.6 21.6 21.6 9.81
32
19
32.8 30.3 9.56 30.0 29.0 11.6 28.0 28.1 11.4 25.5 25.6 10.8 23.8 23.7 10.0
22
35.1 25.1 9.79 32.2 24.0 11.9 30.2 23.2 11.6 27.7 22.2 11.1 26.0 21.6 10.3
Ambient
Power
Return
-15°C
Air
DB
TC
IPT
16
18.3 4.39 20.5 4.93 21.9 5.25 23.7 6.51 24.2 6.57 25.0 6.60 26.3 6.65 26.5 6.67
20
17.0 4.74 19.3 5.28 20.6 5.60 22.5 6.86 23.0 6.92 23.8 6.95 25.0 7.00 25.2 7.02
24
15.8 5.09 18.0 5.63 19.4 5.95 21.2 7.21 21.7 7.27 22.5 7.30 23.8 7.35 24.0 7.37
16
23.0 6.08 25.9 6.83 27.5 7.28 29.9 9.02 30.5 9.11 31.6 9.15 33.1 9.22 33.3 9.24
20
21.5 6.57 24.3 7.31 26.0 7.76 28.3 9.50 29.0 9.59 30.0 9.64 31.5 9.70 31.8 9.72
24
19.9 7.05 22.7 7.80 24.4 8.25 26.7 10.0 27.4 10.1 28.4 10.1 29.9 10.2 30.2 10.2
Outdoor air intake temp(°C D.B.)
20°C
30°C
SHC IPT
TC
SHC IPT
9.6
7.04 25.8
8.8
8.53 24.2
Outdoor air intake temp(°C D.B.)
-10°C
-7°C
TC
IPT
TC
IPT
TC
1-116
TC:Cooling Capacitty
SHC:Sencible Heat Capacity
IPT:Cooling Power Consumption
35°C
40°C
TC
SHC IPT
TC
SHC IPT
8.3
8.36 22.2
7.6
9.5
TC:Cooling Capacitty
IPT:Cooling Power Consumption
0°C
2°C
4°C
IPT
TC
IPT
TC
IPT
www.ampair.co.uk | sales@ampair.co.uk
unit : kW
46°C
TC
SHC IPT
7.95 20.8
7.1
7.38
9.9
7.38
11.1 26.0
8.9
10.3
unit : kW
7°C
10°C
TC
IPT
TC
IPT