Procedure
Procedure
Siemens
Building Technologies
Chimney sweep function
The chimney sweep function produces the operating state required for measuring
emissions/flue gas.
w Navigation to special operation menu is described in Section "Operate special
functions [➙ 66]".
1. Select "Chimney sweep mode" = "On".
The function is activated. The additional operating line "Burner output" is
displayed.
2. Conclude the function with "Chimney sweep function" = "Off".
SLT test (safety limit thermostat test)
Notes on STB test are available in user's guide for your controller.
w Navigation to special operation menu is described in Section "Operate special
functions [➙ 66]".
1. Press and hold the control knob.
a The function is active. The additional operating line "Boiler temperature" is
displayed.
2. End the function by releasing the control knob.
Graphical User Interface UI400
Appendix
11
Special operations
95
CE1U2348en
2014-06-03