Siemens Albatros2 Technical Manual page 89

Graphical user interface ui400
Hide thumbs Also See for Albatros2:
Table of Contents

Advertisement

Used as
Zone assignment
Examples
Siemens
Building Technologies
No. Operating line
40* Used as
* AVS74: Operator unit 1...3 only
Basic principle: the number (1, 2, or 3) after the room unit or operator unit indicates
the zone (1, 2, or 3) controlled by the operator unit.
Additional assignments are available for room unit/operator unit 1 on zones 1 to 3
(zone assignment: Operating lines 42 to 48).
No. Operating line
42
Assignment device 1
44
Operation zone 2
46
Operation zone 3
47* Room values device 1
48
Warmer / Cooler device 1 None ¦ Zone 1 only ¦ For all assigned zones
* Operating lines only available on QAA74
The following example illustrates applications available using the settings "Used
as" (operating line 40) together with "Zone assignment" (operating lines 42 to 48).
Available zones 1 and 2 can be centrally operated from one room unit 1.
Room values (e.g. temperature) on room unit 1 is only be relevant to zone 1 since
the climate in zone 2 (bedrooms) differs from zone 1 (e.g. living area).
The Warmer/Cooler function on room unit 1 acts on zone 1 only.
A room unit 2 allows for separate temperature measurement and individual
operation of zone 2.
Settings for the example:
QAA74, unit 1
Operating line 40
Room unit 1
Operating line 42
Zone 1 and 2
Operating line 47
Zone 1 only
Operating line 48
Zone 1 only
Unit 2
Operating line 40
Room unit 2
Graphical User Interface UI400
Room/operator unit parameters
Settings
Room unit 1 ¦ Room unit 2 ¦ Room unit 3 ¦ Operator unit 1
¦ Operator unit 2 ¦ Operator unit 3
Settings
Zone 1 ¦ Zone 1 and 2 ¦ Zone 1 and 3 ¦ All zones
Jointly with zone 1 ¦ Independently
Jointly with zone 1 ¦ Independently
Zone 1 only ¦ For all assigned zones
Appendix
11
89
CE1U2348en
2014-06-03